3.8. Module – pi626 / pi726 (digital output module)
DESCRIPTION
This definition will open a single PI626 or PI726.
OEM PARAMETERS
OEM parameter Valid numbers Description
CHASSIS 2-29 Logical chassis and slot number where the CIO_DO is located.
SLOT 1-15
PHYSICAL MODULE:
RACK 1: (DO)
32 BOOLEAN outputs
RACK 2: (DIAG)
2 INTEGER inputs
Word 1 Diagnostic bits
bit 0 Slice A
=1 slice is not responding or there is an error
=0 slice is responding
bit 1 Slice B
=1 slice is not responding or there is an error
=0 slice is responding
bit 2 Slice C
=1 slice is not responding or there is an error
=0 slice is responding
bit 3 Module offline or missing
=1 offline or missing
=0 online
bit 4 Single slot hot repair
=1 in progress
=0 not in progress
bit 5 Discrepancy errors
=1 faults detected
=0 no faults detected
bit 6 LFD faults
=1 faults detected
=0 no faults detected
Word 2 Slot number of active module