4 Flash Firmware Kit
Publication 1770-5.9 - May 1998
Reset Module Parameters
Important: Before you reset the parameters, make sure you record
any configuration information stored in the module.
1. Find the View, Data, and Exit buttons on the button of the
module as shown below.
2. Press View and Data simultaneously to reset the module to
factory default values.
3. Set the baud rate to 38.4K as follows:
a. Press the View button until Parameter 2 displays.
b. Press the Data button until 38 displays.
4. Save the settings by simultaneously pressing View and Exit.
Important: If your computers serial port cannot run at a baud
rate of 38.4K, then change the module’s baud rate
(parameter #2) accordingly.
5. Connect the COM card of your computer to the module.
6. Check the STATUS LED on the front of the module as shown in
the figure to the left. It should be solid green. The Channel A
status indicator LED should be flashing red. If the module is not
behaving in this manner, call Technical Support at 440-646-6800.
7. Check your model number. If it is a:
•1770-KFC, go to the next section, “Upgrade the 1770-KFC
Firmware”.
•1770-KFCD, go to page 6, “Upgrade the 1770-KFCD
Firmware”.
SAVE
VIEW DATA EXIT
30580-M
Bottom of Module
ControlNet Communication Interface
HOST
AB
STATUS
30579-M
Front of Module