FACTORYTALK VIEW INSTALLATION GUIDE
128
• • • • •
Set up HMI server redundancy
To restore Server #2 to its original role as the secondary HMI server, set up HMI server
redundancy for Server #1.
To set up redundancy for the HMI server
1. On Server #1, in FactoryTalk View Studio, open the restored, migrated application.
2. In the Explorer window, right-click the HMI server, and then click
Properties
.
3. In the General tab, ensure that the option,
Load and run startup components
when operating system initializes
, is selected.
4. Ensure that
Server #1
is displayed in the field, Computer hosting the server.
5. In the Redundancy tab, select the check box,
Provide redundancy using a
secondary server
.
6. In the field, Computer hosting the server, type
Server #2
.
7. Select a switchover option for the redundant HMI server pair, and then click
OK
.
Set up data server redundancy
To restore Server #2 to its original role as the secondary data server, set up data server
redundancy for Server #1.
To set up redundancy for the data server
1. On Server #1, in the FactoryTalk View SE Administration Console, right-click the
data server (RSLinx Enterprise), and then click
Properties
.
2. In the General tab, ensure that
Server #1
is displayed in the field, Computer hosting
the RSLinx Enterprise server.
3. In the Redundancy tab, select the check box,
Provide redundancy using a
secondary server
.
4. In the field, Computer running secondary server, type
Server #2
.
5. Select a switchover option for the redundant data server pair, and then click
OK
.
Replicate primary server files to the secondary server
Before restarting the entire application, synchronize server settings and content on
Server #1 and Server #2, by replicating files from the primary to the secondary server.
Servers set up to start On demand cannot be made redundant.
FTViewSEInstallENU.book Page 128 Wednesday, July 16, 2014 10:53 AM