11 SETTING UP HMI TAG ALARMS
11–43
• • • • •
11 • Placeholder
Ways to stop HMI tag alarm monitoring
To stop alarm monitoring only, use any of these methods:
In the Graphics editor, create a button object with AlarmOff as the press action. Alarm
monitoring will stop when the button is pressed.
In the Graphics editor, attach Touch animation to a Graphic object, with AlarmOff as
the action. Alarm monitoring will stop when the object is touched.
In the Events editor, type the AlarmOff command in the Action box for an event.
At the command line in FactoryTalk View Studio (or the FactoryTalk View SE
Administration Console), type AlarmOff and then press Enter.
You can also stop alarm monitoring by stopping all HMI server components running on
the computer. For details, see “To stop HMI server components manually” on page 6-19.
If the HMI server performing alarm monitoring is not in the home area, in the preceding
examples, you must include the area name in the AlarmOff command. For details about using
the AlarmOff command, see the FactoryTalk View Site Edition Help.