Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012 37
Create DeviceNet Network Software Files Chapter 2
10. If your drive has not been previously used, skip to step 12.
11. If your PowerFlex 70 drive has
been used previously, reset it to
factory defaults.
a. Click the Parameters tab.
b. From the Parameter 197, Reset
to Defalts pull-down menu,
choose Factory.
c. Click Apply.
12. Use the pull-down menus to
change the following parameters.
13. Click OK.
ID Parameter Required
Value
90 Speed Ref
ASel
DPI Port 5
361 Digital In1 Sel Not used
362 Digital In2 Sel Not used
IMPORTANT
In this example, you do not
need to change any other
parameters because this quick
start does not include a motor.
In real-world applications, the
drive is always connected to,
and controls, a motor. In that
case, you must change
additional parameters, for
example, parameters 41…45.
Optional Selection
Required Selections