Configuring the UDC Module’s Registers
3-57
Meter Port 3
UDC Module Meter Port 3 Register Number Register 1010
UDC register number (0 - 2044) to be mapped to meter port 3.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write
UDC Module Meter Port 3 Bit Number Register 1011
Bit number of the UDC register specified in register 1002 that is to be
mapped to port 3. Enter a value of 100 (bit 00) to 115 (bit 15) as
required. Enter a value of zero if all of the register’s bits are to be
displayed.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write
UDC Module Meter Port 3 Maximum Value Register 1012
Set this register to the number that will represent +10V. The
maximum allowable value is 32767.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write
UDC Module Meter Port 3 Minimum Value Register 1013
Set this register equal to the number that will represent -10V. The
minimum allowable value is -32768.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write