202 Drive Fault Register (Continued)
Btt: 6
Hex Value:
0040H
Sug. Var. Name:
FLT_FLD@
Range:
N/A
Access:
Read Only
UDC Error Code: 1006
LED: PM. FLT on the PMI Processor module
Description:
The Field Loss Fault bit will be set when:
l The field current feedback value is less than the Field Loss Trip Point parameter value entered during
configuration for 5 times the electrical time constant of the field. This assumes FLD_RUN@ (register
100/1 100, bit 4) has been turned on.
0
The field current feedback value dips below the Field Loss Trip Point parameter for 30 msec. after the
field has been turned on.
Bit: 7
Hex Value: 0080H
Sug. Var. Name:
FLT_TAC@
Range:
N/A
Access:
Read Only
UDC Error Code: 1007
LED: FDBK OK on the Resolver
&
Drive I/O module
Description: The Speed Feedback Loss Fault bit is set when the motor’s CEMF is greater than 40%
of the rated armature voltage value entered as a configuration parameter and the speed feedback
signal is less than 5% of the motor base speed as entered as a configuration parameter. This bit is
not used if the No Speed Feedback option is selected as a configuration parameter.
Bit: 8
Hex Value:
01 OOH
Sug. Var. Name:
FLT_TBW@
Range:
N/A
Access:
Read Only
UDC Error Code: 1008
LED: FDBK OK on the Resolver
&
Drive
l/O
module
Description: The Motor Speed Feedback Broken Wire Fault bit is set if a sine or cosine signal being
used for speed or other application feedback is missing due to a broken wire or the resolver gain
tunable
(RES_GAN%)
being set too low. This bit is always tested if a resolver is used. This bit is not
set if No Speed Feedback is selected during parameter entry and register 101 /1 101, bit 10 is set.
Refer to register 101/1 101, bit 10 for more information.
Bit: 9
Hex Value: 0200H
Sug. Var. Name:
FLT_RES@
Range:
N/A
Access:
Read Only
UDC Error Code: 1009
LED: N/A Description: The Resolver Fault bit is set when a blown fuse is detected on the Resolver &
Drive
l/O
module.
3-27