ICS Regent
®
PD
-
6017
Industrial Control Services
1
Relay Output Modules
Low Power and High Power
(T3446L and T3446H)
Issue 1,
March, 06
Relay output modules provide control of eight user output
loads. Two types of relay output modules are available
providing dry contact relay closure outputs for switching a
variety of AC and DC voltages to field loads. Each module's
triplicated I/O Safetybus interface ensures that no Regent
system failure can incorrectly apply power to an output and
that no failure in the module can affect the operation of the
Regent system or other I/O modules in the system.
Features
·
Eight isolated, d
ry contact relay outputs: four Form
-
C, and four
form
-
A or Form
-
B selectable.
·
Hot replaceable.
·
Automatic self
-
testing of triplicated I/O Safetybus circuits and
many simplex logic circuits.
·
High power modules (T3446H) operate up to 250 VAC/125
VDC switching loads rated at 500 VA or 100 Watts.
·
Low power modules (T3446L) operate up to 125 VAC/VDC
switching loads rated at 60
VA or 30 Watts.
·
Individual front panel indicators on each module show active
and fault status, shutdown state, and output status (logic
side).
·
TÜV certified, Risk Class 5, non
-
interfering.
Vista de pagina 0
1 2 3 4 5 6 ... 19 20

Indice de contenidos

Pagina 1 - ICS Regent

ICS Regent® PD-6017 Industrial Control Services 1 Relay Output Modules Low Power and High Power (T3446L and T3446H) Issue 1, March, 06 Relay output

Pagina 2 - Module Operation

Relay Output Modules (T3446L, H) 10 Industrial Control Services Figure 5. Jumper Locations. Operating Envelope Figure 6 shows the voltage and

Pagina 3 - Front Panel Indicators

(T3446L, H) Relay Output Modules PD-6017 Mar-06 11 As with any relay, operating at higher voltages and currents will result in decreased relay li

Pagina 4 - Industrial Control Services

Relay Output Modules (T3446L, H) 12 Industrial Control Services 1010010001000010000000.4 0.8 1.2 1.622.41010010001000010000000.4 0.8 1.2 1.622.4

Pagina 5

(T3446L, H) Relay Output Modules PD-6017 Mar-06 13 Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower lef

Pagina 6 - Application

Relay Output Modules (T3446L, H) 14 Industrial Control Services Figure 8. Installing Slot Keys. Configuration Each output module is configured

Pagina 7

(T3446L, H) Relay Output Modules PD-6017 Mar-06 15 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Se

Pagina 8 - Output Form Selection

Relay Output Modules (T3446L, H) 16 Industrial Control Services Name Also called the tag name, this is the name used in the application program to

Pagina 9

(T3446L, H) Relay Output Modules PD-6017 Mar-06 17 control logic by using a contact element (or similar element) with the output point name. Main

Pagina 10 - Operating Envelope

Relay Output Modules (T3446L, H) 18 Industrial Control Services Specifications Safetybus Power 1.0 load units Number of Outputs Eight isolated cir

Pagina 11

(T3446L, H) Relay Output Modules PD-6017 Mar-06 19 Fusing (internal) One 3.5 A, slow blow per output Note: Internal fuses are for protection of

Pagina 12 - Relay Protection

Relay Output Modules (T3446L, H) 2 Industrial Control Services Module Operation A block diagram of a typical relay output module is shown in Figu

Pagina 13 - Fault Mode Jumper

Relay Output Modules (T3446L, H) 20 Industrial Control Services

Pagina 14 - Configuration

(T3446L, H) Relay Output Modules PD-6017 Mar-06 3 logically turned off, the relay coil is de-energized (closing the N.C. contact). The relay pro

Pagina 15

Relay Output Modules (T3446L, H) 4 Industrial Control Services Shutdown Indicator Upon loss of communications with the controller, output modules

Pagina 16 - Programming

(T3446L, H) Relay Output Modules PD-6017 Mar-06 5 Figure 2. Relay Output Module.

Pagina 17 - Safety Considerations

Relay Output Modules (T3446L, H) 6 Industrial Control Services Application Simplex Configuration Relay output modules provide a suitable interfac

Pagina 18 - Specifications

(T3446L, H) Relay Output Modules PD-6017 Mar-06 7 Figure 4. Module Wiring.

Pagina 19

Relay Output Modules (T3446L, H) 8 Industrial Control Services Voltages greater than 50 volts, or of different polarities or phase, should not be

Pagina 20 - (T3446L, H)

(T3446L, H) Relay Output Modules PD-6017 Mar-06 9 Jumper Form Description E110 NO1 Selects normally open for relay 1 E111 NC1 Selects normally c