ICS Regent
®
PD
-
6019
Industrial Control Services
1
DC Guarded Digital Output Modules
24 VDC, 48 VDC and 120 VDC
(T3461A, T3462A and T3468A)
Issue 1,
March, 06
DC Guarded output modules provide Guarded switching of
user
-
supplied DC voltages to a maximum of eight field loads.
These
modules are called Guarded because each module's
dual
-
redundant design ensures that no single fault within the
module will inadvertently apply power to an output.
Extensive fault detection and redundant critical circuits
ensure that each module operates in a fail
-
safe manner.
Features
·
Eight Guarded output circuits configured as two sepa
rately
powered groups of four circuits each.
·
Fault tolerant operation when connected in parallel with
an
other module of the same type.
·
Hot
-
replaceable.
·
100% self
-
testing of all critical circuits.
·
Individual front panel indicators on each module show active
and fault, shutdown state, blown fuse, and output on/off status
(logic side).
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5.
Two Guard
ed output modules can be connected in parallel to
obtain fault tolerant control of power to loads. In this parallel
module configuration, either module can be removed and
replaced while the other Guarded module continues to control
the loads without interruption.
Vista de pagina 0
1 2 3 4 5 6 ... 19 20

Indice de contenidos

Pagina 1 - ICS Regent

ICS Regent® PD-6019 Industrial Control Services 1 DC Guarded Digital Output Modules 24 VDC, 48 VDC and 120 VDC (T3461A, T3462A and T3468A) Issue 1,

Pagina 2 - Module Operation

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 10 Industrial Control Services module. In this way, the two FETs of each output circuit are

Pagina 3

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 11 Figure 6. Fail-Safe Field Wiring.

Pagina 4

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 12 Industrial Control Services Figure 7. Fault Tolerant Field Wiring.

Pagina 5

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 13 Fault Mode Jumper The fault mode jumper is located behind the ID switch co

Pagina 6

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 14 Industrial Control Services Figure 8. Installing Slot Keys. Configuration Each output

Pagina 7

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 15 1) Set the Module Type: Position the cursor on the module slot you wish t

Pagina 8 - Actuators

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 16 Industrial Control Services Name Also called the tag name, this is the name used in the ap

Pagina 9 - Field Wiring

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 17 To program fault tolerant outputs two output coils driven by the same cont

Pagina 10 - Important!

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 18 Industrial Control Services Specifications Safetybus Power 0.85 load units Number of Outpu

Pagina 11

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 19 Isolation 2500 volts minimum (field wiring to control logic) 2500 volts mi

Pagina 12 - Industrial Control Services

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 2 Industrial Control Services Module Operation A block diagram of a typical monitored Guarde

Pagina 13

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 20 Industrial Control Services

Pagina 14 - Configuration

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 3 energized. This combination of series output switches and independent dri

Pagina 15

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 4 Industrial Control Services majority-voted result to the processors produces an I/O module

Pagina 16 - Programming

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 5 When an output switch failure or blown fuse is detected a module fault con

Pagina 17 - Safety Considerations

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 6 Industrial Control Services Figure 2. A DC Guarded Output Module.

Pagina 18 - Specifications

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 7 Blown Fuse Indicators The red BLOWN FUSE indicators switch on when the adj

Pagina 19

DC Guarded Digital Output Modules (T3461A, 62A, 68A) 8 Industrial Control Services In the fault tolerant configuration, a failed module can be re

Pagina 20

(T3461A, 62A, 68A) DC Guarded Digital Output Modules PD-6019 Mar-06 9 Figure 5. Fault Tolerant Configuration with Redundant Actuators. Field