(T3461A, 62A, 68A) DC Guarded Digital Output Modules
PD
-
6019
Mar
-
06
17
To program fault tolerant outputs two output coils driven by
the same control logic are used as shown in Figure
11
.
Figure
11
. Programming Fault Tolerant Outputs.
In this illustration A, B, C, D represent various logic elements
used to drive the outputs; XV103A represents the output on
one Guarded output module; and XV103B represents the
output on the other Guarded output module.
Maintenance
No periodic maintenance or calibration is required for this
module.
Fuses can be removed and replaced without removing the
module from the I/O chassis. Turning the fuse holder one
-
quarter turn from its lo
cked position releases the fuse holder,
extending the fuse and allowing it to be removed.
To prevent damage to the module, replacement fuses must be
of the same rating and type (see Specifications, below).
Safety Considerations
The DC Guarded output modules are TÜV certified to Risk
Class 5 for safety critical outputs. The modules are approved
for de
-
energize to trip safety critical outputs in single or dual
module configurations.
The modules are also approved for energize to
trip safety
critical outputs in dual module configuration
only
if the
outputs are dynamically transitioned at a period not greater
that six months (to verify the signal wiring and load device
integrity).