Isolated Guarded Digital Output Module
(T7485)
18
Industrial Control Services
quarter turn from its locked position releases the fuse holder,
extending the fuse and allowing it to be removed.
To prevent damage to the module, replacement fuses must be
of the same rating and type (see Specifications, below).
Safety Considerations
The Isolated Guarded output module is TÜV certified to Risk
Class 5 for safety critical outputs. The modules are approved
for de
-
energize to trip safety critical outputs in single or dual
module configurations.
The modules are also approved for energize to trip safety
critical outputs in dual module configuration
only
if the
outputs are dynamically transitioned at a period not greater
that six months (to verify the signal wiring and load device
integrity).
Specifications
Safetybus Power
1.75 load units
Number of Outputs
Eight, isolated
Voltage Range
12 to 130 VAC
15 to 150 VDC
Frequency Range (Vac)
47 to 63 Hz
Output Load Current (I
out
)
(0 to 40
°
C)
derating (at 60
°
C)
2.0 amps max. (see page
10
)
1.5 amps max. (see page
10
)
Module Load Current (I
mod
)
for I
out
< 1.5 amps
for I
out
> 1.5 amps
12 amps (0 to 40
°
C), derated
linearly to 8 amps at 60
°
C
8 amps (0 to 40
°
C), derated
linearly to 6 amps at 60
°
C
On State
Drop
2.5 volts, maximum
Surge Current
20 amps, 20 msec