Isolated Guarded Digital Output Module
(T7485)
20
Industrial Control Services
Electromagnetic
Interference
IEC 801 Part 2
-
Electrostatic
Discharges
IEC 801 Part 3
-
Radiated
Electromagnetic Fields
IEC 801 Part 4
-
Transients
and Bursts
IEC 801 Part 5
-
Surge
Immunity
ANSI/IEEE C37.90
-
Surge
Withstand Capability
Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz
-
500 MHz
Level 4: 2 kV, 2.5 kHz for
t=60 sec
Level 3: 2 kV
2.5 kV damped 1 MHz sine
wave,
4 kV bi
-
directional impulse,
10 nsec rise time, fast
transient
Safety
Certified to DIN V VDE
0801 for Risk Class 5. Also
designed to meet UL 508 and
CSA 22.2, No. 142
-
M1981
Dimensions
Height:
Width:
Depth:
12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)
Weight
4.2 lbs (1.8 kg)