Trusted
TM
Toolset Suite T8082
Issue 14 Feb 10 PD-T8082 24
2. Output Modules
This section defines the mapping between the output state and the front panel indicators for the
specific module. The mapping defines the required operation for all output channels. An LED mapping
entry is made using the syntax shown below.
state# = <OFF | RED | GREEN [+FLASH]>
I
f no entries are made in this section, the module will operate with the default LED mapping. The
example in Table 3 below shows defaults for the 8451 Digital Output Module, which are suitable for
outputs without line monitoring devices installed.
0 = Off Not used
1 = Red No field supply voltage
2 = Off Output de-energised (off)
3 = Green Line open circuit
4 = Green Output energised (on)
5 = Red Field short circuit
6 = Off Not used
7 = Off Not used
8- = Red
Table 3 8451 Output Module LED Default Settings
Note: States 8 through 15 all represent channel fault states.
Input and Output Module LED templates are configured using the Module LED State Editor. On
creating an LED template, selectModule in the LED Config section. The Module LED State Editor is
described in section 2.3.7 below.
2. Zone Interface Modules
Trusted
TM
8448 Zone Interface Modules can have each channel defined as an input or an output using
a Channel Template. In this case, one single LED definition for all channels is not appropriate. The
LED states for this module are configured using the Channel LED State Editor. On creating an LED
template, selectChannel in the LED Config section. The Channel LED State Editor is described in
section 2.3.8 below.