2.15. Uploading to the EWS
The System.INI file may be uploaded from the Trusted
TM
TMR Processor by selecting the Upload the
.INI Buffer From MP button on the tool bar of the System Configuration Manager screen, shown in
Figure 41 below.
Figure 41 Upload INI Buffer from MP Icon
Selection of the Upload the .INI Buffer From MP button starts the process of uploading the
System.INI file to the EWS. Whilst this is taking place, the Communications in progress window
shown below is displayed as shown in Figure 42 below.
Figure 42 Communication in Progress Window
The System.INI file is transmitted in packets of data. The TX LED in the Communications in
progress window flashes as each packet of data is being uploaded. The RX flashes to indicate that a
packet has been successfully uploaded.
The Cancel button changes to OK when all data has been successfully uploaded. When this has
occurred, the user must select OK to return to System Configuration Manager screen.