Issue 13 April 10 PD-T8402 15
2.4. Trusted
TM
Module Polarisation/Keying.
All Trusted
TM
Modules have been Keyed to prevent insertion into the wrong position within a chassis.
The polarisation comprises two parts. The module and the associated field cable.
Each module type has been keyed during manufacture. The organisation responsible for the
integration of the Trusted
T
M
system must key the cable by removing the keying pieces from the cable
so that they correspond with the bungs fitted to the associated module prior to fitting.
1
12
Cable Exit
Release button
Polarising/Keying
Pins.
(Remove using
side cutters where
identified below)
Trusted Cable
hood
Smart
Swap
Connector
if Fitted
Figure 3 Module polarisation
For Cables with Companion slot installations both keying strips must be polarised.
For This Module (T8402) remove keying pins 1,3,4.