Trusted
TM
Module T8402
Issue 13 April 10 PD-T8402 28
6. Specifications
System Supply Range 20 to 32V dc
Number of Inputs 60 Channels
Input Voltage
Measurement Range ±40V dc
Maximum Withstanding ±50V dc
Input voltage monitor absolute accuracy 0.5V dc Full Scale
Sample Update Time 0.5ms
Turn-on/off Voltage Configurable
Circuit Type Fault tolerant, with optional line
monitoring
Fusing None, external if required
Intrinsic Safety External barrier
Sequence of Events
Event Resolution
Time-stamp Accuracy
1ms
±0.5 ms
Field Common Isolation
Sustained Working
Maximum Withstanding
±250V dc
±2.5kV dc
Channel to Channel Crosstalk -40 to –60 dB
Power Consumption 15 – 18W
External Power
Expected current consumption @ 24V dc
4.8mA per channel
Input Impedance 5K ohm
Self-Test Interval 2 minutes
Operating Temperature
-5°C to 60°C (23°F to 140°F)
Non-operating Temperature
-25°C to 70°C (-13°F to 158°F)
Temperature change 0.5ºC/min
Operating Humidity 5 – 95% RH non-condensing
Environmental Specifications Refer to Document 552517
Dimensions
Height
Width
Depth
266mm (10.5ins)
31mm (1.2ins)
303mm (12.0ins)
Weight 1.16kg (2.6lbs)
Real Time Clock Resolution
100µSec