
Chapter 3
Configuration & Interfacing
3–4
Discrete Input The MCA board has a single discrete input which can be programmed for
use in the Drive. Figure 3–2 shows this input and the parameters that
control its use.
Figure
3-2. Discrete Input
J5
1
2
Stop
3
4
J4
115VAC/24VDC
Select
Bit # Specifier Parameter
520
Operator
519
0
1
2
•
•
•
15
518
300
301
•
•
•
314
J4
Position Input
1
– 2
2 – 3
24VDC
115VAC
!
ATTENTION: The Start/Stop circuitry in this drive is
composed of solid-state components. If hazards due to
accidental contact with moving machine components or
unintentional flow of liquid, gas or solids exist, NEMA
standards require that a hardwired maintained contingency Stop
circuit such as the one shown at terminals 1–2 of J5 be used
with this Drive.
Position Input Type
1 – 2
2 – 3
Table
3-A.
Discrete Input Voltage Select Jumper J4
24V
DC
115V AC Input
Par Num Par Type
518
519
520
Table
3-B.
Parameter Listing for Discrete Input
Setup
Setup
Setup
Description
Discrete Input Map
Parameter Bit# Specifier
Parameter Operator
Discrete Input Map Parameter (Par #518) – Determines which
parameter the discrete input will affect. Valid source parameters are 300 –
314.
Comentarios a estos manuales