All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM027A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
Buer Unit
Buering with electrolytic capacitors instead
of lead batteries
Buering of 48V loads
Minimum hold-up time 0.1s at 20A and 0.2s at 10A
Longer hold-up time at lower loads
Clear status indication by status LED and signaling
terminals
Quick-connect spring-clamp terminals
3 year warranty
1. Description
2. Specication Quick Reference
Rated voltage DC 48V
Voltage range 48-56V
Output voltage 45V or
V
IN
–2V
Buer mode
select with jumper
Output current 0 to 20A
Hold-up time
min 0.1s 45V, 20A
typ 0.15s 45V, 20A
min 13.4s 45V, 0.1A
typ 21s
45V, 0.1A
Charging current
max 500mA
Charging time
typ 21s
Input current typ 40mA standby mode
Power dissipation typ 1.9W standby mode
Temperature range
-25°C to +70°C operational
Dimensions 64x124x102mm WxHxD
The buer unit is a supplementary device for regulated
DC48V power supplies. It buers load currents during
typical mains faults and load peaks.
Working principle
In times when the power
supply provides sucient
voltages, the buer unit
stores energy in integrated electrolytic capacitors. In case of
mains voltage fault, this energy is released again in a
regulated process.
Bridges mains faults
without interruption
Statistic show that 80% of
all mains fault lasts less
than 0.2s. These mains
faults are completely bridged by the buer unit. This
increases the reliability of the system as a whole.
Extended hold-up time
Once mains power fails or
is switched o, the buer
unit will continue to
provide the load current
for a dened period of time. Process data can be saved and
processes can be terminated before the DC power switches
o. Controlled restarts are subsequently possible.
Easy to handle, expandable and maintanance-free
The buer unit does not require
any control wiring. It can be
added parallel to the load circuit
at any given point. Buer units
can be switched in parallel to
increase the output ampacity or the hold-up time.
DC
Charge
Discharge
Buffer
AC
DC
Buffer Unit
AC
DC
Buffer Unit
DC
Buffer
Unit(s)
Power
Supply
Load
AC
+
-
3. Catalog Numbers
4. Certication Marks
Buer Unit
1606-XLSBUFFER48
48V, 20A, 200ms
Accessory 1606-XLB Wall mounting
bracket
UL 508
UL 60950-1
EMC, LVD
C-Tick
GOST R