8. Functional Diagram
Fig. 8-1 Functional diagram
Buffer Capacitor
Charger &
Inrush Limiter
Buffer
Capacitor
Buffer Capacitor
Discharger
Status
lamp
7 Active
6 +
Ready Monitor
+
-
Active Monitor
+
-
Optokoppler
Optokoppler
8 Ready
9 Inhibit
Optokoppler
Buffer
Capacitor
Shut-Down
Input / Output
Voltage Monitor
Back-up
Level
Selector
Reverse-
Polarity
Protection
-
-
+
+
Safety and
Over-
Voltage
Protection
Chassis
Ground
9. Front Side and User Elements
Fig. 9-1 Front side
A. I/O Power Port
Quick-connect spring-clamp
terminals,
+ Positive terminal
- Negative terminal
Chassis Ground
to bond the housing
B. Status lamp
OFF: Buer is discharged, or
terminal voltage is below 22V
ON: Unit is fully charged
Flashes 1,25Hz:
Unit is in charging mode
Flashes 10Hz:
Unit is in discharging mode
C. Signal Port
Plug Connector
6 common + pole
7
Active : unit is buering
8
Ready: unit is on stand-by
9
Inhibit : initiates buer
discharging and inhibits
recharging of capacitors
D. Back-up threshold jumper
1-2: Variable mode
Unit switches to buer mode when input
voltage decreases by 1V within 1.1V/s or
the input voltage falls below 45V.
2-3: Fixed mode, (factory setting)
Unit switches to buer mode as soon as the
voltage falls below 45V
Missing jumper = 45V xed
Set the unit to xed mode:
-
when using other power supplies
than the 1606-XLS series
-
with back-feeding loads
-
when the buer unit is placed close to
the load
-
whenever in doubt
Set the unit to variable mode:
-
for 48V applications
-
when the buer unit is placed close to
the power supply
A
B
C
D