All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
8 Rockwell Automation Publication 1606-RM027A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
12. Terminals and Wiring
Power terminal
Type Bi-stable, quick-connect spring clamp terminals. IP20 Finger-safe construction.
Suitable for eld- and factory installation. Shipped in open position.
Solid wire 0.5-6mm
2
Stranded wire 0.5-4mm
2
AWG 20-10AWG
Ferrules Allowed, but not required
Pull-out force 10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E)
Wire stripping length 10mm / 0.4inch
Fig. 12-1 Connecting a wire
Instructions:
a) Use appropriate copper cables designed
for an operating temperature of 60°C.
b) Follow national installation codes and regulations.
c) Ensure that all strands of a stranded wire are fully
inserted in the terminal connection.
d) Up to two stranded wires with the same cross-
section are permitted in one connection point.
1. Insert the wire 2. Snap the lever
To disconnect wire : reverse above procedure.
Signal terminal
Type Plug connector with screw terminal mechanism.
Finger-touch-proof terminal with captive screws for 3.5mm slotted screwdriver.
Solid / stranded wire
0.2-2.5mm
2
AWG 22-14AWG
Ferrules
up to 1.5 mm
2
wire gauge
Wire stripping length 6mm / 0.24inch
Tightening torque 0.4Nm, 3.5lb.in
13. Reliability
Lifetime expectancy min. 41 000h 40°C, stand-by mode
min. 116 000h 25°C, stand-by mode
MTBF SN 29500, IEC 61709 2 348 000h 40°C, stand-by mode
4 231 000h 25°C, stand-by mode
MTBF MIL HDBK 217F 405 000h 40°C, stand-by mode, ground benign GB40
636 000h 25°C, stand-by mode, ground benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specied in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturer specication.
MTBF means Mean Time Between Failures, which is calculated according to statistics of device failures, and
indicates reliability of a device. It is the statistical representation of the likelihood of failure of a given device, and