Rockwell-automation 1738-ADNX ArmorPoint DeviceNet Adapters, Series A Manual de usuario Pagina 15

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 14
ArmorPOINT I/O DeviceNet Adapters 15
Publication
1738-IN014D-EN-E - December 2010
Mounting base screw torque M4 (#8) screw
0.86 Nm (7.5 lb-in) in Aluminum
1.81 Nm (16 lb-in) in Steel
Wiring category
(1)
1 – on power ports
1 – on communications ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to publication 1770-4.1,
Industrial Automation Wiring and Grounding Guidelines.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, non-operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 Mhz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 Mhz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
(1738-ADN12, 1738-ADN18 and 1738-ADN18P only)
General Specifications
Vista de pagina 14
1 2 ... 10 11 12 13 14 15 16

Comentarios a estos manuales

Sin comentarios