Publication 1738-UM001A-EN-P - February 2005
B-12 Quick Start For the 1738-ADNX
Right now, the 1738-ADNX is not in another scanner’s scanlist so
you can use the Auto Start Mode feature. By using Auto Start
Mode, the 1738-ADNX will map all the devices on the Subnet
and automatically adjust the value for the following parameters:
1, Max Backplane MACID
9, Poll/COS Connection Consume Size
10, Poll Connection Produce Size
11, COS Connection Produce Size, and
12, Strobe Connection Produce Size.
2. Select the pulldown box next to the Auto Start Mode parameter.
You can map the data using the four options discussed earlier. If
you choose to use the Map Data With Fixed Map Size option, the
map size is selected with parameter 7, Fixed Map Size.
3. For this example, choose Map Data To Word Boundaries as shown
below: