Rockwell-automation 1771-CFM Config. Flowmeter Installation Instructio Manual de usuario Pagina 13

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 12
Configurable Flowmeter Module 13
Publication 1771ĆIN043B-EN-P - July 2002
Modes of Operation
You configure the CFM module for these modes of operation:
Use this mode To
Indicators/
Alarms
Prover
Total
reset
Scaler
values
Rollover
value
Totalizer
accurately measure counts using a flowmeter
or positive displacement meter
trigger outputs directly from the CFM module
Ċ trigger on total, frequency, acceleration
monitor flow total, rate, and rate of change
independent of your PLC processor scan times
store counts based on external input
scale the frequency and count to
engineering units
interface to a prover
overrange
overflow
overspeed
acceleration
Nonresettable Totalizer
operate in the Totalizer mode with the count
reset function disabled to prevent loss of
accumulated value
overrange
overflow
overspeed
acceleration
HighĆresolution Frequency
1
(channels 0&1 or channels 2&3)
monitor the frequency of an input with high
accuracy (e.g. shaft)
monitor the rate of speed change
operate outputs based on speed or
rate of change
scale the frequency to engineering units
overspeed
overrange
acceleration
Direction Sensor
1
(channels 0&1 or channels 2&3)
monitor the direction of shaft rotation
monitor rate of change and frequency
trigger outputs based on direction, frequency,
rate of change
scale the frequency and count to
engineering units
overspeed
acceleration
overrange
1
This mode uses two channels for one input (your input device is connected to F0 or F2, while F1 or F3 is unused).
In this mode
of operation
You can assign outputs that are programmable to trigger
Totalizer
on total, rate, rate change (acceleration), total overflow or
prover status
Nonresettable Totalizer
on total, rate, rate change (acceleration), total overflow or
prover status
HighĆresolution
Frequency
on frequency or frequency rate of change (acceleration)
Direction Sensor
on either CLOCKWISE or COUNTERĆCLOCKWISE direction,
acceleration or frequency (outputs are triggered ON only)
If you want to configure the module You
through I/O Configuration software (if you
are using a PLCĆ5 family processor
1
)
enter the appropriate information on the
CFM module edit screens.
by editing bits at the address of the
BTW instruction
edit the data file addresses in the BTW
instruction to match your particular
application. Use the word assignments
on page 14 to edit the bits that apply to
your application(s).
1
See PLCĆ5 Programming Software I/O Configuration Manual, publication 6200Ć6.4.12, for
supported processors.
Vista de pagina 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 19 20

Comentarios a estos manuales

Sin comentarios