Configurable Flowmeter Module14
Publication 1771ĆIN043B-EN-P - July 2002
BTW Word Assignments
Bit
Á
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Block ID & Resets
1 Header Prover Run Initialize Overflow Reset Total Reset
Output 1 and Output 0 Trigger & Select
2 Output 1 Trigger Tie Output 1 to Channel Output 0 Trigger Tie Output 0 to Channel
Output 3 and Output 2 Trigger & Select
3 Output 3 Trigger Tie Output 3 to Channel Output 2 Trigger Tie Output 2 to Channel
Input Channel Operating Mode
4 Channel 3 Channel 2 Channel 1 Channel 0
Input Channel Configuration
Channel 0 (words 5Ć14) Channel 1 (words 15Ć24) Channel 2 (words 25Ć34) Channel 3 (words 35Ć44)
5, 15, 25, 35
Frequency
in 10ths
Bandwidth
Limit
Sampling
Termination
4x
High Hz
Prover
Type
Debounce
Filtering
Acceleration Calculation Time
6, 16, 26, 36 Minimum Frequency Sampling Time
7, 17, 27, 37 Number of Pulses to Terminate Sampling
8, 18, 28, 38 Highest Allowable Frequency
9, 19, 29, 39 Acceleration Alarm Value (what rate to trigger on)
10, 20, 30, 40
Frequency Scaler Multiplier
Â
Frequency Scaler Divisor
Â
11, 21, 31, 41
Total Scaler Multiplier
Â
12, 22, 32, 42
Total Scaler Divisor
Â
13, 23, 33, 43 Rollover Value Ċ Most Significant Digit (0Ć999 x 10,000)
14, 24, 34, 44 Rollover Value Ċ Least Significant Digit (0Ć9,999)
Output Configuration
Output 0 (words 45Ć48) Output 1 (words 49Ć52) Output 2 (words 53Ć56) Output 3 (words 57Ć60)
45, 49, 53, 57 Output ON value Ċ Most Significant Digit (0Ć999 x 10,000)
46, 50, 54, 58 Output ON value Ċ Least Significant Digit (0Ć9,999)
47, 51, 55, 59 Output OFF value Ċ Most Significant Digit (0Ć999 x 10,000)
48, 52, 56, 60 Output OFF value Ċ Least Significant Digit (0Ć9,999)
À
Valid BTW lengths are: 0, 1, 2, 3, 4, 14, 24, 34, 44, 48, 52, 56, 60.
Á
ALL numeric values are in binary.
Â
When scaling is used, all outputs are still controlled by the actual value not the scaled value.
For detailed BTW descriptions,
see chapter 4, (publication
1771Ć6.5.99).