Configurable Flowmeter Module 15
Publication 1771ĆIN043B-EN-P - July 2002
Your PLC processor gets data from the CFM module using BTR
instructions in your ladder logic program. The CFM module
transfers up to 41 words to the PLC processors data table file.
The words contain module status and input data from each channel.
You should program a block transfer read length of zero (0). When a
BTR of 0 is programmed, the CFM module will determine the
correct number of words (41) to return.
BTR Word Assignments
Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Block ID & Resets
1 Header
PowerĆup
bit
Output Status & Diagnostics
2
Output Status
Error Words & Diagnostics
Mode Indication
3 Channel 3 Channel 2 Channel 1 Channel 0
Channel 1 Status Channel 0 Status
4
Prover Status
Overrange
Alarm
Overflow
Status
Overspeed
Alarm
Acceleration
Alarm
Prover Status
Overrange
Alarm
Overflow
Status
Overspeed
Alarm
Acceleration
Alarm
Channel 3 Status Channel 2 Status
5
Prover Status
Overrange
Alarm
Overflow
Status
Overspeed
Alarm
Acceleration
Alarm
Prover Status
Overrange
Alarm
Overflow
Status
Overspeed
Alarm
Acceleration
Alarm
Input Channel Data
Channel 0 (words 6Ć14) Channel 1 (words 15Ć23) Channel 2 (words 24Ć32) Channel 3 (words 33Ć41)
6, 15, 24, 33 Percent of Full Scale (Rate % of High RPM value)
7, 16, 25, 34 Frequency (0Ć120 ) MSD
8, 17, 26, 35 Frequency (0Ć999) LSD
9, 18, 27, 36 Total MSD (0Ć999)
10, 19, 28, 37 Total LSD (0Ć9,999)
11, 20, 29, 38 Acceleration (rate of change of frequency)
12, 21, 30, 39 Direction
13, 22, 31, 40 Prover Total Count Value or Store Count Value Ċ MSD (0Ć999)
14, 23, 32, 41 Prover Total Count Value or Store Count Value Ċ LSD (0Ć9,999)
not used
* Numeric values are in binary except for Diagnostics (word 2, bits 00Ć07)*
For detailed BTR descriptions,
see chapter 5, (publication
1771Ć6.5.99).
Interpret Module Status