Number of Input Channels
4
Module Location
1771ĆA1B, ĆA2B, A3B, ĆA3B1, ĆA4B (series A and B) I/O chassis
1771ĆAM1, ĆAM2 I/O chassis with integral power supply, adapter
Maximum Count Value 0-9,999,999 (programmable)
BTW Processing Time (worst case) 5.5ms Ċ on a configuration change
Module Scan Time 1.3-5ms (depending on configuration and frequency)
Maximum Input Frequency
100kHz @ flowmeter Input (maximum frequency is 120kHz Ć
100kHz @ gate input overrange occurs at 100kHz)
Inputs per Channel
2 - flowmeter input Ċ used for all modes
gate input Ċ used in Totalizer and Nonresettable Totalizer modes
Flowmeter (F0-F3) Input Voltage
50mVĆ30V ac Ċ Magnetic Pickup
5Ć30V dc (TTL compatible)
Bently 33005&8mmĊProximity Pickups
Flowmeter (F0-F3) Input Impedance 5KΩ ± 30% resistive
Gate (G0-G3) Voltage 5-12 and 12-30V dc
Gate (G0-G3) Current 22mA maximum
Number of Outputs 4
Maximum Output OffĆstate Leakage Current less than 300μA @ 30V dc
Maximum OnĆstate Voltage Drop 0.6Ω x current
Output Control
Any number of outputs are assignable to any of 4 channels.
One turn-on" value and one turn-off" value per output.
Output Voltage 5 to 30V dc, customer supplied
Output Current
1A per channel sourced out of module
All outputs can be on simultaneously without derating.
Output Switching Time
outputs triggered by Total: turn ON < 100μs; turn OFF < 100μs
all other turn ON and OFF times < 1ms
Filtering (F0ĆF3 inputs) Ċ jumper selectable highĆspeed or lowĆpass filter jumper (filter = below 70Hz)
Debouncing (G0ĆG3 inputs) Ċ software selectable
1s (approximate) between transitions with no minimum pulse width Ċ
Totalizer and Nonresettable Totalizer modes only
Module dc Source Output 24V dc; 12mA; ripple: ±5%; noise: 240mV peakĆtoĆpeak
Backplane Current 0.8A maximum, 5V dc
Customer Supply 5 to 30V dc
Isolation Voltage
Tested to withstand - for 60s
500V between input and backplane,
1500V between output and backplane,
500V between isolated channels,
1500V between isolated outputs and gates
Module Power Dissipation 13W (maximum); 2W (minimum)
Module Thermal Dissipation 54.2 BTU/hr (maximum); 6.8 BTU/hr (minimum)
Maximum Adjacent Slot Power Dissipation 11W
Input Conductors Wire Type
Category
Length
Belden 8761
Category 2
1
304.8m (1000ft)
Output Conductors Wire Size
Category
14AWG (2.5mm
2
) solid or stranded copper wire rated @ 60
o
C or greater
Category 2
1
Specifications