7-4
Publication 1771Ć6.5.116 - May 1996
When bits 9 and 10 in block transfer write word 3 are set for “two’s
complement – data first configuration,” the block transfer read will
have the channel data first in the transfer.
Figure 7.2
Block Transfer Read in Two's Complement - Data First Configuration, SingleĆended
Inputs
Dec. Bits 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Description
Octal Bits 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Description
Word 1 Channel 1 Input Channel 1 Input
2 Channel 2 Input Channel 2 Input
3 Channel 3 Input Channel 3 Input
4 Channel 4 Input Channel 4 Input
⇓⇓
16 Channel 16 Input Channel 16 Input
17 HF EE CS RTS IS OR PU Diagnostics
18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data underrange for channels 1-16
1
19 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data overrange for channels 1-16
1
20 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data polarity for channels 1-16
21 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Offset Calibration Results
22 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Gain Calibration Results
23 15Ćbit rolling counter - binary, 1ms resolution Time Stamp
24 Update rate - binary, to 1υs, with +4µs resolution Scan Time
Where: PU = Power up bit
OR = Out of range bit
IS = Invalid scaling bit
RTS = Real time sampling bit
HF = Hardware Fault
EE = EEPROM status bits
CS = Calibration status bits
1
These bits are set (1) at approximately the input range limits selected (Table NO TAG).
Data First Configuration