Quick Reference Section
Appendix A
A4
Table A.B
Instruction
Execution V
alues
Note: These values are approximate (in average microseconds) exectuion values per scan.
Instruction Name Symbol
Instruction
True
Instruction
False
Examine on, Examine off -||-,-|/|- 10 5
Output Energize -()- 19 19
Output Latch -(L)- 19 15
Output Unlatch -(U)- 19 15
Get -(G)- 27 -
Put -(PUT)- 22 15
Equal -(=)= 22 5
Less Than -(<)- 31 5
Get Byte -|B|- 11 -
Limit Test -|L|- 23 5
Counter Reset -(CTR)- 23 15
Retentive Timer Reset -(RTR)- 24 16
Timer On-delay -(TON)- 140 60
Retentive Timer On-delay -(RTO)- 140 48
Retentive Timer On-delay -(TOF) 145 70
Up Counter -(CTU)- 130 110
Down Counter -(CTD)- 135 115
Add -(+)- 48 15
Subtract -(-)- 80 19
Multiply -(x)-(x)- 615 60
Divide
-
(÷)−(÷)-
875
Add to any of the above
when its address is
400
8
or greater 27 27
Master Control Reset -(MCR)- 23 20
Zone Control Last State -(ZCL)- 28 81+
Branch Start 18 13
Branch End 18 13
End, Temporary End T.END 27 27