ControlNet-to-DeviceNet Linking Device 37
Publication
1788-IN052D-EN-P - February 2007
View and Interpret Controller Status Tags
Use the following procedure to troubleshoot the DeviceNet network
using the controller status tags in RSLogix5000 software.
1. Use RSLogix5000 software to verify that the controller is in run
mode and that the program is online with the controller.
2. In the program’s organization tree, double-click Controller
Tags.
The Controller Tags display.
96 Communication port is in test mode. None.
97 The controller has placed the scanner
in halt mode.February
If the
O.CommandRegister.HaltScanner
bit is on, turn it off then cycle
scanner power.
98 General firmware error. Replace device.
99 System Failure. Replace device.
DeviceNet Status Codes
Status Code Description of Status Recommended Action
Double-click to
open.