CompactBlock Distributed I/O on Remote I/O Series D 29
Publication
1791R-IN002B-EN-P - August 2003
Maximum Output Data Format (Base Modules -16B0)
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 O15 O14 O13 O12 O11 O10 O9 O8 O7 O6 O5 O4 O3 O2 O1 O0 Base
1 Reserved Analog Output Data Channel 0
2 Reserved Analog Output Data Channel 1
3 OE HLS R IF IR3 IR2 IR1 IR0 IM3 IM2 IM1 IM0 OR1 OR0 OM1 OM0
4 Reserved
5 Reserved
OM x Output Mode Selection Set “0”: Voltage Mode Set “1”: Current Mode
OR x Output Range Selection on Current ModeSet “0”: 4-20mA Set “1”: 0-20mA
IM x Input Channel Mode Select Set “0”: Voltage Mode Set “1”: Current Mode
IR x Input Range Select on Current Mode Set “0”: 4-20mA Set “1”: 0-20mA
IF Input Filter Selection Set “0”: 50Hz Set “1”: 60Hz
R Reserved;
HLS HLS/OFF Set “0”: Output Reset Set “1”: Hold Last State
OE Output Enable Set “0”: Output Disabled Set “1”: Output Enabled
(Output is 0mA at 0-20mA mode and 4-20mA mode
and 0V at 0-10V mode when this bit is 0)
Maximum Input Data Format (Base Modules -8B8P or -8V8P)
Bit Position
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Reserved In7 In6 In5 In4 In3 In2 In1 In0 Base
1 Reserved Analog Input Data Channel 0
2 Reserved Analog Input Data Channel 1
3 Reserved Analog Input Data Channel 2
4 Reserved Analog Input Data Channel 3
5 URo1 URo0 ORo1 ORo0 OW3 OW2 OW1 OW0 ORi3 ORi2 ORi1 ORi0 Reserved RF UF
UF Module Unrecoverable Fault Set “0”: No Error Set “1”: Error
RF Module Recoverable Fault Set “0”: No Error Set “1”: Error
ORi x Over Range Input Channel Set “0”: No Over Range Set “1”: Over Range
OW x Input Open Wire (@ 4-20mA Range) Set “0”: No Open Wire Set “1”: Open Wire
ORo x Output Data Over Range Set “0”: No Over Range Set “1”: Over Range
URo x Output Data Under Range (@4-20MA Range)Set “0”: No Under Range Set “1”: Under Range