Publication 1794-6.5.11 - September 2011
Install Your FLEX I/O Frequency Input Module 23
Wiring Connections for the Frequency Input Module
Channel 0 Terminals
(5)
Channel 1 Terminals
(5)
Types of Inputs Power Input
RET
(7)
Power Input
RET
(7)
GND
(5)
Frequency
24V DC IEC1+ Proximity
(1)
(2)
7638912
24V DC Contact Switch
(3)
7638912
500mV AC Magnetic Pickup
7
(6)
53 8 1012
50mV AC Magnetic Pickup
(4)
7 5 3 8 10 12
6V AC Vortex 2 1 3 13 14 12
3V AC Vortex 2 0 3 13 15 12
Gate
24V DC IEC1+ Proximity
(1) (2)
24 23 20 25 26 29
24V DC Contact Switch
(3)
24 23 20 25 26 29
500mV AC Magnetic Pickup 24 22 20 25 27 29
50mV AC Magnetic Pickup
(4)
24 22 20 25 27 29
(1)
As defined by standard IEC 1131-2.
(2)
RET not used on 2-wire devices.
(3)
Add external resistor from 24V to F or G for wire-off detection (0.4 mA) – (≈ 50 KΩ ).
(4)
Add a jumper between 50 mV and RET (Frequency – channel 0 = 3…4; channel 1 = 11…12)
(Gate – channel 0 = 21…20; channel 1 = 28…29).
(5)
Connect cable shields to GND terminals.
(6)
24V terminal may not be used on 2-wire magnetic devices.
(7)
All 4 RET terminals (ch 0 and 1, Freq, Gate) are internally connected together.
Total current draw through the terminal base unit is limited to 10 A.
Separate power connections to the terminal base unit may be
necessary.