Publication 1794-6.5.11 - September 2011
Read and Write Configuration Maps for the FLEX I/O Module 47
Word 6 Bit 07 Initiate Startup Select (channel 1) – Alerts a channel that if process startup is in
progress to defeat the missing pulse alarm for a time determined by the missing pulse
delay multiplier.
0 = Normal run mode,
1 = Startup Mode – Defeat/delay Missing Pulse Alarm
Default = 0 – Normal run mode
Bits 08…11
(10…13)
Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms)
the module will spend collecting pulses to determine the Frequency.
Bit 11 10 09 08 Minimum Frequency Sampling Time (in ms)
00002
00014
00105
001110
010020
010150
0 1 1 0 100
0 1 1 1 200
1 0 0 0 500
1 0 0 1 1000
1010…1111 not used – 2 ms default sample time used
Bit 12 (14) Invert Select – Frequency Input (channel 1) – Selects whether to invert the Frequency
input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally
Open relay or switch contact on the 24V DC Frequency Input terminal. Allows
compatibility with an Active Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed
relay contact on the 24V DC Frequency Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default = 0 – Normal (Active High, 24V = On)
Bit/Word Definitions for the Block Transfer Write Words
Word Bit
Definition