Publication 1794-6.5.11 - September 2011
32 Configure Your FLEX I/O Module with RSLogix 5000 Software
6. On the Configuration tab, specify the following:
Channel
Frequency or Acceleration
If you choose Frequency, go to step 8. Go to step 9 if you choose
Acceleration.
7. For Frequency mode, specify the following:
Maximum Frequency
Frequency Range
Minimum Frequency Sample Time
8. For Acceleration mode, specify the following:
Maximum Frequency
Frequency Range
Minimum Frequency Sample Time
Acceleration Calculation Time
9. Click the Alarms tab and specify the following:
Missing Pulse Multiplier
Missing Pulse Delay Multiplier
Pulses to Terminate Sampling
Wire-off/Missing Pulse Fault Select Mode
10. Click OK on the Module Properties dialog after you have configured the
different parameters.
The following options are available for each parameter on the Configuration
and Alarms tabs of the Module Properties dialog.