Read and Write Configuration Maps for the FLEX I/O Module 37
4 R R Direction
Ch 0
GS
Ch 0
F/A
Ch 0
WO
Ch 0
MPA
Ch 0
R R Direction
Ch 1
GS
Ch 1
F/A
Ch 1
WO
Ch 1
MPA
Ch 1
5 Reserved Diagnostic Status
Where: R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm
Block Transfer Read Word Assignments
(Octal Bit) 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Decimal Bit15141312111009080706050403020100
Bit/Word Definitions for Block Transfer Read Words
Word Bit Definition
Read
Word 0
Bit 00…15
(00…17)
Calculated value of frequency (channel 0) – frequency can be reported down to 1 or 1.0 Hz, depending on
the Frequency Range bit setting:
Below a 1 Hz value, 0 is reported
Below a 1.0 Hz value, 0.0 is reported.
Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier.
Word 1 Bit 00…15
(00…17)
% of Full Scale or Acceleration (channel 0) – Value of the calculated frequency scaled by the Maximum
Frequency, or Calculated Value of Acceleration in Hz/s, depending on the state of the Frequency or
Acceleration Alarm Select bit.
Note: Percentage Full scale is calculated accurately up to a maximum of 3,276.7%. Beyond this maximum,
the value of 3,276.7% will be returned, and a Calculation Failure (9) will be set in the Diagnostic Status
byte.
Word 2 Bit 00…15
(00…17)
Calculated value of Frequency (channel 1) – Frequency can be reported down to 1 or 1.0 Hz, depending on
the Frequency Range bit setting; below a 1 Hz value, 0 is reported; below a 1.0 Hz value, 0.0 is reported.
Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier.
Word 3 Bit 00…15
(00…17)
Percentage of Full Scale or Acceleration (channel 1) – Value of the calculated Frequency scaled by the
Maximum Frequency, or Calculated Value of Acceleration in Hz/s, depending on the state of the Frequency
or Acceleration Alarm Select bit. Percentage full scale will be calculated accurately up to a maximum of
3,276.7%. Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in
the Diagnostic Status byte.