16 FLEX Ex 8 Output and HART Analog Modules
Publication
1797-5.3 - September 2011
1797-OE8 Output Map (Write Words)
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 OE FR Reserved DD
Ch7
DD
Ch6
DD
Ch5
DD
Ch4
DD
Ch3
DD
Ch2
DD
Ch1
DD
Ch0
1 Channel 0 Output Data
2 Channel 1 Output Data
3 Channel 2 Output Data
4 Channel 3 Output Data
5 Channel 4 Output Data
6 Channel 5 Output Data
7 Channel 6 Output Data
8 Channel 7 Output Data
Where: Res = reserved, Ch = channel
DD = digital data, FR = fault reset
OE = output enable
1797-OE8H Output Map (Write Words)
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Res FR Reserved DD
Ch7
DD
Ch6
DD
Ch5
DD
Ch4
DD
Ch3
DD
Ch2
DD
Ch1
DD
Ch0
1 Channel 0 Output Data
2 Channel 1 Output Data
3 Channel 2 Output Data
4 Channel 3 Output Data
5 Channel 4 Output Data
6 Channel 5 Output Data
7 Channel 6 Output Data
8 Channel 7 Output Data
Where: Res = reserved, Ch = channel
DD = digital data, FR = fault reset