Rockwell-automation 1797-OE8H FLEX Ex 8 Output Analog Modules Manual de usuario Pagina 23

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 22
FLEX Ex 8 Output and HART Analog Modules 23
Publication
1797-5.3 - September 2011
HART Input Data Descriptions
Chn: HART CMD 3 Communication
Status
0: HART CMD3
Communication Disabled or
No Error
1: HART CMD3
Communication Error
between Adapter &
Module
Chn: HART Comm Status (HART CMD3
Response first status byte):
Refer to User Manual
Chn: HART Field Device Status (HART
CMD3 Response second status byte):
Refer to User Manual
Chn: HART Loop Status:
Bit 0: HART enable
Bit 1: Device Connected
Bit 2: Response Error
Bit 3: CMD 48 Update
Bit 4: HART Loop Tolerance Error
Bit 5: HART Update
Bit 6: HART message
Bit 7:
0: Disabled
0: Not Connected
0: No HART message
failure
0: CMD 48 not
updated
0: No HART Current
Fault
0: HART Device
information not
updated
0: No new message
1: Enabled
1: Connected
1: Response ended in error
1: CMD 48 updated
1:HART Current Fault
1: HART Device information
updated since last read
1: HART user message queue
has completed a message
Reserved
Where PVA = The primary variable for this channel has been acquired.
SVA = The secondary variable for this channel has been acquired.
TVA = The tertiary variable for this channel has been acquired.
FVA = The fourth (quaternary) variable for this channel has been acquired.
Vista de pagina 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 51 52