Rockwell-automation 1797-OE8H FLEX Ex 8 Output Analog Modules Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
FLEX Ex 8 Output and HART Analog Modules 17
Publication
1797-5.3 - September 2011
1797-OE8H Configuration Map
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 LFM VR FE
Ch7
FE
Ch6
FE
Ch5
FE
Ch4
Byte
Order
Group B
HS
LEDs
HSI FE
Ch3
FE
Ch2
FE
Ch1
FE
Ch0
Byte
Order
Group A
1HD
Ch7
HD
Ch6
HD
Ch5
HD
Ch4
HD
Ch3
HD
Ch2
HD
Ch1
HD
Ch0
HHE
Ch7
HHE
Ch6
HHE
Ch5
HHE
Ch4
HHE
Ch3
HHE
Ch2
HHE
Ch1
HHE
Ch0
2 Data Format Ch3 Data Format Ch2 Data Format Ch1 Data Format Ch0
3 Data Format Ch7 Data Format Ch6 Data Format Ch5 Data Format Ch4
4 HART Read Back
Threshold Ch1
FLE
Ch1
AFM
Ch1
HART Read Back
Threshold Ch0
FLE
Ch0
AFM
Ch0
5 HART Read Back
Threshold Ch3
FLE
Ch3
AFM
Ch3
HART Read Back
Threshold Ch2
FLE
Ch2
AFM
Ch2
6 HART Read Back
Threshold Ch5
FLE
Ch5
AFM
Ch5
HART Read Back
Threshold Ch4
FLE
Ch4
AFM
Ch04
7 HART Read Back
Threshold Ch7
FLE
Ch7
AFM
Ch7
HART Read Back
Threshold Ch6
FLE
Ch6
AFM
Ch06
8DF
Ch7
DF
Ch6
DF
Ch5
DF
Ch4
DF
Ch3
DF
Ch2
DF
Ch1
DF
Ch0
DM
Ch7
DM
Ch6
DM
Ch5
DM
Ch4
DM
Ch3
DM
Ch2
DM
Ch1
DM
Ch0
9 Fault Value Ch0
10 Fault Value Ch1
11 Fault Value Ch2
12 Fault Value Ch3
13 Fault Value Ch4
14 Fault Value Ch5
15 Fault Value Ch6
16 Fault Value Ch7
17 HR
Ch7
HR
Ch6
HR
Ch5
HR
Ch4
HR
Ch3
HR
Ch2
HR
Ch1
HR
Ch0
HC
Ch7
HC
Ch6
HC
Ch5
HC
Ch4
HC
Ch3
HC
Ch2
HC
Ch1
HC
Ch0
Where LFM = local fault mode VR = verify replacement
FE = fault enable HD = HART disable
HHE = HART handheld enable FLE = fault latch enabled
AFM = analog fault mode DF = digital fault mode
DM = digital mode HR = HART rebuild
HC = HART CMD3 disable
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 51 52

Comentarios a estos manuales

Sin comentarios