FLEX Ex 8 Output and HART Analog Modules 43
Publication
1797-5.3 - September 2011
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V
oc
< 5.8V; I
sc
< 400 mA.
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V
oc
< 9.5V; I
sc
< 1 A.
To any IS device with Entity
Concept parameters of
(V
max
, I
max
, C
i
, L
i
)
appropriate for connection
to associated apparatus
with Entity Concept
parameters listed in Table 2.
1797-OE8
16
Shield Connection
Only
50
51
35
34
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus
Connector
33
40
41
42
43
44
45
0 (+)
Female Bus
Connector
1 (-)
4 (+)
5 (-)
8 (+)
9 (-)
12 (+)
13 (-)
17 (+)
18 (-)
21 (+)
22 (-)
25 (+)
26 (-)
29 (+)
30 (-)
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
42016
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (V
max
, I
max
, C
i
, L
i
)
appropriate for connection to
associated apparatus with
Entity Concept parameters
listed in Table 1.