18 Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter 2 Installing the Option Module
Setting the IP Address
Selection Jumper
The IP Address Selection Jumper (Figure 1) determines the source of the
network address for the option module.
Figure 1 - Setting the IP Address Selection Jumper
Using Default Network Address
When the jumper is on Pins 2 and 3 and Device Parameter 16 - [DHCP] is set to
‘0’ (Disabled), the following default network address is used:
IP Address 192.168.0.1
Subnet Mask 255.255.255.0
Gateway 192.168.0.1
Using DHCP Server
When the jumper is on Pins 1 and 2 and Device Parameter 16 - [DHCP] is set to
‘1’ (Enabled), the network address is configured from a DHCP server. To set an
IP address using a DHCP server, do the following.
1. Set Device Parameter 16 - [DHCP] to ‘1’ (Enabled) to select the DHCP
server as the source for the IP address.
2. Reset the option module; see Resetting the Option Module
on page 33, so
it can get the new IP address from the DHCP server.
Using Option Module Parameters
When the jumper is on Pins 1 and 2—or there is no jumper—and Device
Parameter 16 - [DHCP] is set to ‘0’ (Disabled), the network address is
configured with option module parameters.
1
3
2
Pin 2 and 3 (DEFAULT setting)
Pin 1 and 2 (CONFIG setting) to
use option module parameters or
DHCP server for network address