42 Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter 4 Using BACnet Services and Objects
BV10 Run/Stop Read/write the drive’s Run/Stop command. Turn on this object to start the
drive/turn off bit to stop the drive.
Logic
Command
Word, Bit 18
✔✔
BV11 Rev/Fwd Read/write the drive’s Rev/Fwd command. Turn on this object to
command the reverse direction when the drive is running. Turn off this
object to command Forward.
Logic
Command
Word, Bits 4
and 5
✔✔
BV12 Ref2/Ref1 Read/write the drive’s Ref2/Ref1 command. Turn on this object to select
the Reference 2 instance of the AV object as the drive’s speed reference.
Turn off this object to select Reference 1.
Logic
Command
Word, Bits
12, 13, and
14
✔✔
BV13 Clear Faults Read/write the drive’s Clear Faults command. Turn on this object to clear
the drive fault. Turning off this object does nothing.
Logic
Command
Word, Bit 3
✔✔
BV14 Auto/Manual Read/write the drive’s Auto/Manual setting.
0 = Not manual; 1 = Manual
Logic
Command
Word, Bit 6
✔✔
Table 3 - BACnet Object Descriptions and Supported Drives (Continued)
Object Name Use this Object to... Drive
Parameter
Number
PowerFlex 750-
Series Drive
753 755