Configuring the Option Module Chapter 3
2. Set the value of Device Parameters 04 - [IP Addr Cfg 1] through 07 - [IP
Addr Cfg 4] to a unique IP address.
3. Reset the option module; see Resetting the Option Module
on page 33.
Set the Subnet Mask
1. Verif y that Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).
2. Set the value of Device Parameters 08 - [Subnet Cfg 1] through 11 -
[Subnet Cfg 4] to the desired value for the subnet mask.
3. Reset the option module; see Resetting the Option Module
on page 33.
Set the Gateway Address
1. Verif y that Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).
2. Set the value of Device Parameters 12 - [Gateway Cfg 1] through 15 -
[Gateway Cfg 4] to the IP address of the gateway device.
3. Reset the option module; see Resetting the Option Module
on page 33.
ESC
ENTER
Stopped
0.00 Hz
AUTO
Edit IP Addr Cfg 1
0
0 << 255
F
Default = 0.0.0.0 255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Stopped
0.00 Hz F
Edit Subnet Cfg 1
0
0 << 255
ENTER
ESC
AUTO
Default = 0.0.0.0 255.255.255.255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
ESC
ENTER
AUTO
F
Edit Gateway Cfg 1
0
0 << 255
Stopped
0.00 Hz
Default = 0.0.0.0 255.255.255.255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]