Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Manual de usuario Pagina 112

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 296
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 111
5-20 Using the I/O
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Figure 5.11 ControlLogix Example Ladder Logic Program Using a Drive Generic
Profile for PowerFlex 750-Series Drives Datalink Scaling
For PowerFlex 750-Series drives, the destination tag can be a REAL or
DINT. Make the destination tag the same data type as the parameter being
read. For information on Datalink scaling, see page 5-9
.
TIP: When using a drive that has 16-bit Datalinks (PowerFlex 70,
PowerFlex 700, and PowerFlex 700H drives) to transfer a 32-bit parameter,
two contiguous drive Datalink parameters (for example, Data Out A1/A2,
B1/B2, and so forth) are required. To determine if a parameter is a 32-bit
parameter, see the Parameter section in the drive documentation and look
for a symbol in the ‘No.’ column. (All parameters in PowerFlex 700
Series B drives are 32-bit parameters.) For example, parameter 3 - [Output
Current] in a PowerFlex 70 EC drive is a 32-bit parameter. When using a
drive that has 32-bit Datalinks (PowerFlex 700 VC, PowerFlex 700S, and
PowerFlex 750-Series drives), only one drive Datalink parameter is required
to transfer any parameter.
32
Vista de pagina 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 295 296

Comentarios a estos manuales

Sin comentarios