Page 26 AutoMax DCSNet /RE RIO Module
Publication number 56AMXN-UM002A-EN-P November 2002
Figure 6 Module Properties 1
7. Set the module RPI. This is how often the module’s scheduled data
is updated in the processor. The value can range from 3.0 to 750 ms.
The default is 3 ms. The listen only RPI should match the RPI for
the owning ControlLogix.
8. Click Finish >> to complete the module configuration.
9. Save the program and download it to the ControlLogix processor.
Remote I/O Master
To configure the module in RSLogix 5000, you must be offline.
1. If you are creating a new project, select File/New to create a new
project, give the processor a name, and enter the slot it occupies in
the ControlLogix rack.
2. Right click on I/O configuration and select New Module…
3. Select a module of Type 1756-MODULE, Description Generic 1756
Module from the list and Click OK. RSLogix 5000 displays the
Module Properties – Local dialog box.