Rockwell-automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM Manual de usuario Pagina 1

Busca en linea o descarga Manual de usuario para Equipo Rockwell-automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM. Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 420
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente

Indice de contenidos

Pagina 1 - SCADA System

SCADA SystemApplication Guide

Pagina 2 - Important User Information

Publication AG-UM008C-EN-P - February 20056 Table of Contents Configuring a Standard-Mode DF1 Half-Duplex Master Station . . . . . .

Pagina 3 - Summary of Changes

Publication AG-UM008C-EN-P - February 20053-32 Configuring MicroLogix 1100/1200/1500 ControllersFigure 3.5 Applying Store and Forward with DF1

Pagina 4

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-33Configuring a Station on a Point-to-Point Link

Pagina 5 - Table of Contents

Publication AG-UM008C-EN-P - February 20053-34 Configuring MicroLogix 1100/1200/1500 ControllersDefine the communication parameters shown in Ta

Pagina 6 - 1100/1200/1500 Controllers

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-35DF1 Full-Duplex Channel StatusChannel Status da

Pagina 7 - 5/05 Processors

Publication AG-UM008C-EN-P - February 20053-36 Configuring MicroLogix 1100/1200/1500 ControllersDF1 Messaging Messaging can occur between: • a

Pagina 8 - Chapter 5

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-37Processor-to-Processor A processor-to-processor

Pagina 9 - Chapter 7

Publication AG-UM008C-EN-P - February 20053-38 Configuring MicroLogix 1100/1200/1500 ControllersFor both Point-to-Multipoint and Point-to-Point

Pagina 10 - Configuring Modems

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-39To continue the example, if Message Retries is

Pagina 11 - Table of Contents 7

Publication AG-UM008C-EN-P - February 20053-40 Configuring MicroLogix 1100/1200/1500 ControllersStandard Polling Mode With Multiple Message Tra

Pagina 12

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-41Message Timeout value should be at least (Slave

Pagina 13 - Sample Ladder Logic

Publication AG-UM008C-EN-P - February 2005Table of Contents 7DATA-LINC Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23SR

Pagina 14 - Glossary

Publication AG-UM008C-EN-P - February 20053-42 Configuring MicroLogix 1100/1200/1500 ControllersExample MSG Control Blocks Figure 3.7 Write M

Pagina 15 - Audience

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-43slave station. For a Logix slave station, a tag

Pagina 16 - Contents of this Manual

Publication AG-UM008C-EN-P - February 20053-44 Configuring MicroLogix 1100/1200/1500 ControllersFigure 3.9 Write MSG from a MicroLogix 1100/120

Pagina 17 - Address Conventions

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-45Figure 3.10 Read MSG from a MicroLogix 1100/12

Pagina 18 - Related Publications

Publication AG-UM008C-EN-P - February 20053-46 Configuring MicroLogix 1100/1200/1500 ControllersModbus RTU ProtocolThis section provides the co

Pagina 19 - Designing Communication

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-47by 1, and selects the appropriate memory group

Pagina 20 - Choosing a Polling Mode

Publication AG-UM008C-EN-P - February 20053-48 Configuring MicroLogix 1100/1200/1500 ControllersModbus RTU Master ConfigurationSelect the Modbu

Pagina 21

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-49When the system driver is Modbus RTU Master, th

Pagina 22

Publication AG-UM008C-EN-P - February 20053-50 Configuring MicroLogix 1100/1200/1500 ControllersModbus RTU Slave ConfigurationThe Modbus RTU Sl

Pagina 23

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-514. Enter the data table size and type for each

Pagina 24 - Addressing Tips

Publication AG-UM008C-EN-P - February 20058 Table of Contents Appendix AModem Cable ReferenceAppendix Objective . . . . . . . . . . .

Pagina 25

Publication AG-UM008C-EN-P - February 20053-52 Configuring MicroLogix 1100/1200/1500 ControllersModbus AddressingDescription Valid MicroLogix A

Pagina 26 - Standard-Mode

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-53Modbus CommandsThe controller configured for Mo

Pagina 27 - To help you understand See

Publication AG-UM008C-EN-P - February 20053-54 Configuring MicroLogix 1100/1200/1500 ControllersThe controller configured for Modbus RTU Master

Pagina 28 - • plan for timing issues

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-55:Error CodeError Description Transmitted Except

Pagina 29

Publication AG-UM008C-EN-P - February 20053-56 Configuring MicroLogix 1100/1200/1500 ControllersConfiguring a Modbus MessageThis section descri

Pagina 30

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-57This Controller ParametersIf a Channel configur

Pagina 31 - Design Considerations

Publication AG-UM008C-EN-P - February 20053-58 Configuring MicroLogix 1100/1200/1500 ControllersData LoggingData Logging is supported by the Mi

Pagina 32

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-59Example Queue 0This queue is used to show how t

Pagina 33 - Message-Based Mode

Publication AG-UM008C-EN-P - February 20053-60 Configuring MicroLogix 1100/1200/1500 ControllersNumber of RecordsUsing Queue 0 as an example, e

Pagina 34 - Protocol

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-61String Length of RecordThe size of a record is

Pagina 35

Publication AG-UM008C-EN-P - February 2005Table of Contents 9Worksheet 3.4 MicroLogix 1100/1200/1500 DF1 Full-Duplex Point-to-Point Configurati

Pagina 36 - Data table

Publication AG-UM008C-EN-P - February 20053-62 Configuring MicroLogix 1100/1200/1500 ControllersConfiguring Data Log QueuesData Logging is conf

Pagina 37 - What to Do Next?

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-633. The Data Log Que dialog box appears as shown

Pagina 38

Publication AG-UM008C-EN-P - February 20053-64 Configuring MicroLogix 1100/1200/1500 ControllersDLG - Data Log InstructionThe DLG instruction t

Pagina 39

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-65The number of DLS file elements depends upon th

Pagina 40

Publication AG-UM008C-EN-P - February 20053-66 Configuring MicroLogix 1100/1200/1500 ControllersRecords Stored (RST)Records Stored (RST) specif

Pagina 41 - Mode Master Station

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-67The data is retrieved as an ASCII string with t

Pagina 42 - 5 software:

Publication AG-UM008C-EN-P - February 20053-68 Configuring MicroLogix 1100/1200/1500 ControllersInformation for Creating Your Own ApplicationCo

Pagina 43

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-69Controller Responds with ReplyIf the data integ

Pagina 44

Publication AG-UM008C-EN-P - February 20053-70 Configuring MicroLogix 1100/1200/1500 Controllers

Pagina 45

1 Publication AG-UM008C-EN-P - February 2005Chapter 4Configuring SLC 5/03, 5/04, and 5/05 Processors Chapter ObjectivesThis chapter helps you set up

Pagina 46 - Create Station Lists

Publication AG-UM008C-EN-P - February 200510 Table of Contents MicroLogix 1000 Analog DF1 Half-Duplex Slave Report-by-Exception MSG .

Pagina 47 - of the station currently

Publication AG-UM008C-EN-P - February 20054-2 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsOverviewTo configure an SLC 5/03, 5/04, or 5/05 pr

Pagina 48 - B11:2 1111 1111 1111 1111

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-3Using Modems that Support DF1 Communication Protoc

Pagina 49 - Message-based Mode

Publication AG-UM008C-EN-P - February 20054-4 Configuring SLC 5/03, 5/04, and 5/05 Processorsof the RS-232 modem control signals when Half-Dupl

Pagina 50

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-5Modem Control Line OperationThe following explains

Pagina 51

Publication AG-UM008C-EN-P - February 20054-6 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsDF1 Half-Duplex SlaveWhen configured for DF1 half-

Pagina 52

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-7Full-Duplex Modem SelectedDTR and RTS are always a

Pagina 53

Publication AG-UM008C-EN-P - February 20054-8 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsHalf-Duplex with Continuous Carrier SelectedDTR is

Pagina 54

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-9For modems that do not supply a CTS signal but sti

Pagina 55

Publication AG-UM008C-EN-P - February 20054-10 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsConfiguring a Standard-Mode DF1 Half-Duplex Maste

Pagina 56

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-11 Use Worksheet 4.1 (page D-14) for an example con

Pagina 57

1 Publication AG-UM008C-EN-P - February 2005PrefaceWhat SCADA Information Is Available?Two principle SCADA documents are available:• SCADA System App

Pagina 58

Publication AG-UM008C-EN-P - February 20054-12 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsChannel 0 System Baud Rate Select a communication

Pagina 59

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-13Minimum DF1 Half-Duplex Master Channel 0 ACK Time

Pagina 60

Publication AG-UM008C-EN-P - February 20054-14 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsThe timeout must be long enough that after the ma

Pagina 61

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-15Finally, you must determine the larger of two val

Pagina 62

Publication AG-UM008C-EN-P - February 20054-16 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsDF1 Half-Duplex Master Channel StatusChannel Stat

Pagina 63

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-17Monitor Active Stations To see what stations

Pagina 64

Publication AG-UM008C-EN-P - February 20054-18 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsConfiguring a Message-based Mode DF1 Half-Duplex

Pagina 65 - (slave) station 13

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-19Use Worksheet 4.2 (page D-15) for an example conf

Pagina 66 - N15:0 file

Publication AG-UM008C-EN-P - February 20054-20 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsDefine the parameters shown in Table 4.4 when con

Pagina 67 - Control Block

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-21Channel 0 SystemError Detection With this selecti

Pagina 68

Publication AG-UM008C-EN-P - February 20052 Preface Contents of this ManualRefer to the following listing for the contents of this use

Pagina 69 - Controllers

Publication AG-UM008C-EN-P - February 20054-22 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsConfiguring a Slave Station To choose the process

Pagina 70 - Installing the Controller

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-23Use Worksheet 4.3 (page D-16) for an example conf

Pagina 71 - Optical Isolator

Publication AG-UM008C-EN-P - February 20054-24 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsChan. 0 System Poll Timeout The timer keeps track

Pagina 72 - Supplied Optical Isolator

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-25Configuring Channel 0 Poll TimeoutThe Channel 0 P

Pagina 73 - To modem

Publication AG-UM008C-EN-P - February 20054-26 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsLack of Memory/No ACK Sentword 8 The number of ti

Pagina 74

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-27Configuring a Radio Modem StationTo configure an

Pagina 75

Publication AG-UM008C-EN-P - February 20054-28 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsUse Worksheet 4.5 SLC 5/03, 5/04, and 5/05 DF1 Ra

Pagina 76

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-29Chan. 0 System Control Line No Handshaking This p

Pagina 77

Publication AG-UM008C-EN-P - February 20054-30 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsDF1 Radio Modem Channel StatusChannel Status data

Pagina 78 - Only) Selected

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-31Clicking the Clear button while monitoring Channe

Pagina 79

Publication AG-UM008C-EN-P - February 2005Preface 3TermsWe use these terms frequently in this book:See the Glossary for other definitions.Addre

Pagina 80

Publication AG-UM008C-EN-P - February 20054-32 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsFigure 4.4 Applying DF1 Radio Modem ProtocolFigur

Pagina 81

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-33Configuring a Station on a Point-to-Point Link To

Pagina 82

Publication AG-UM008C-EN-P - February 20054-34 Configuring SLC 5/03, 5/04, and 5/05 Processors Use Worksheet 4.4 (page D-17) for an

Pagina 83

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-35DF1 Full-Duplex Channel StatusChannel Status data

Pagina 84

Publication AG-UM008C-EN-P - February 20054-36 Configuring SLC 5/03, 5/04, and 5/05 Processors2. See Table 4.10 for details concerning the DF1

Pagina 85

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-37Messaging Messaging can occur between: • a master

Pagina 86

Publication AG-UM008C-EN-P - February 20054-38 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsProcessor-to-Processor A processor-to-processor m

Pagina 87

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-39For both Point-to-Multipoint and Point-to-Point L

Pagina 88

Publication AG-UM008C-EN-P - February 20054-40 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsTo continue the example, if Message Retries is co

Pagina 89

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-41Therefore, if there are 10 slave stations and the

Pagina 90

Publication AG-UM008C-EN-P - February 20054 Preface Related PublicationsThe following documents contain additional information concern

Pagina 91

Publication AG-UM008C-EN-P - February 20054-42 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsFor this example, the MSG Timeout value should be

Pagina 92

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-43Example MSG Control Blocks Figure 4.6 Write MSG

Pagina 93

Publication AG-UM008C-EN-P - February 20054-44 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsThis MSG example tells the SLC 5/03, 5/04, or 5/0

Pagina 94

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-45This MSG example tells the SLC 5/03, 5/04, or 5/0

Pagina 95

Publication AG-UM008C-EN-P - February 20054-46 Configuring SLC 5/03, 5/04, and 5/05 ProcessorsIn this example, the SLC master station is issuin

Pagina 96

Publication AG-UM008C-EN-P - February 2005Configuring SLC 5/03, 5/04, and 5/05 Processors 4-47In this example, the SLC master station is issuin

Pagina 97

Publication AG-UM008C-EN-P - February 20054-48 Configuring SLC 5/03, 5/04, and 5/05 Processors

Pagina 98

1 Publication AG-UM008C-EN-P - February 2005Chapter 5Configuring SLC 500 Processors with 1747-KE Interface Modules Chapter ObjectivesThis chapter h

Pagina 99

Publication AG-UM008C-EN-P - February 20055-2 Configuring SLC 500 Processors with 1747-KE Interface ModulesFigure 5.1 Configuring SLC 500 Proc

Pagina 100

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-3For details about installing the int

Pagina 101 - Point-to-Point Link

1 Publication AG-UM008C-EN-P - February 2005Chapter 1Designing CommunicationChapter ObjectivesUse this chapter along with the configuration chapters o

Pagina 102

Publication AG-UM008C-EN-P - February 20055-4 Configuring SLC 500 Processors with 1747-KE Interface ModulesConfiguring the 1747-KE Interface M

Pagina 103

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-5Figure 5.3 Configuring the DF1 Port

Pagina 104 - DF1 Messaging

Publication AG-UM008C-EN-P - February 20055-6 Configuring SLC 500 Processors with 1747-KE Interface ModulesParameter SelectionsNode address Sel

Pagina 105 - Processor-to-Processor

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-7Configure the DF1 Protocol Driver Fi

Pagina 106 - Message-based Polling Mode

Publication AG-UM008C-EN-P - February 20055-8 Configuring SLC 500 Processors with 1747-KE Interface ModulesParameter SelectionsDuplicate Packet

Pagina 107 - Standard Polling Mode

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-9Figure 5.6 Configuring the Driver fo

Pagina 108

Publication AG-UM008C-EN-P - February 20055-10 Configuring SLC 500 Processors with 1747-KE Interface ModulesSave the ConfigurationTo save the c

Pagina 109

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-113. Remove interface module. Place t

Pagina 110 - Example MSG Control

Publication AG-UM008C-EN-P - February 20055-12 Configuring SLC 500 Processors with 1747-KE Interface ModulesProcessor-to-Processor An SLC 5/02

Pagina 111

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-13Point-to-Multipoint Link Configurat

Pagina 112 - MicroLogix Controller

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

Pagina 113

Publication AG-UM008C-EN-P - February 20051-2 Designing CommunicationChoosing a Polling Mode for DF1 Half-Duplex MasterA master station can be

Pagina 114 - Modbus RTU Protocol

Publication AG-UM008C-EN-P - February 20055-14 Configuring SLC 500 Processors with 1747-KE Interface ModulesFigure 5.7 Write MSG instruction f

Pagina 115 - Modbus RTU Slave

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-15Note that the SLC 5/02 station addr

Pagina 116

Publication AG-UM008C-EN-P - February 20055-16 Configuring SLC 500 Processors with 1747-KE Interface ModulesFor example, if the SLC 5/02 proces

Pagina 117

Publication AG-UM008C-EN-P - February 2005Configuring SLC 500 Processors with 1747-KE Interface Modules 5-17Figure 5.10 Read MSG instruction f

Pagina 118

Publication AG-UM008C-EN-P - February 20055-18 Configuring SLC 500 Processors with 1747-KE Interface Modules

Pagina 119 - Modbus Slave Memory Map

1 Publication AG-UM008C-EN-P - February 2005Chapter 6Configuring MicroLogix 1000 ControllersChapter ObjectivesThis chapter helps you set up a MicroLog

Pagina 120

Publication AG-UM008C-EN-P - February 20056-2 Configuring MicroLogix 1000 ControllersOverviewTo configure a MicroLogix 1000 controller:1. Conne

Pagina 121 - Modbus Commands

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-3Installing the ControllerFor details about installing the

Pagina 122 - Modbus Error Codes

Publication AG-UM008C-EN-P - February 20056-4 Configuring MicroLogix 1000 ControllersIsolated ConnectionsMicroLogix controllers should be insta

Pagina 123

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-5The following baud rate limitations affect autoswitching:•

Pagina 124 - Configuring a Modbus Message

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-3Standard Polling ModeStandard polling mode is strongly recommended for lar

Pagina 125 - Target Device

Publication AG-UM008C-EN-P - February 20056-6 Configuring MicroLogix 1000 ControllersDial-up Phone ModemsDial-up phone line modems support poin

Pagina 126 - Data Logging

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-7Line DriversLine drivers, also called short-haul modems, d

Pagina 127 - Example Queue 0

Publication AG-UM008C-EN-P - February 20056-8 Configuring MicroLogix 1000 ControllersAn additional feature of the DF1 half-duplex protocol is t

Pagina 128 - Example Queue 5

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-9Ownership TimeoutWhen a program download sequence is start

Pagina 129 - Number of Records

Publication AG-UM008C-EN-P - February 20056-10 Configuring MicroLogix 1000 ControllersConfiguring a Slave StationTo choose the controller as a

Pagina 130 - Configuring Data Log Queues

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-11Table 6.1 DF1 Half-duplex Slave Configuration Parameters

Pagina 131

Publication AG-UM008C-EN-P - February 20056-12 Configuring MicroLogix 1000 Controllersamount of delay time after activating RTS to wait before

Pagina 132 - Data Log

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-13Configuring a Point-to-Point StationTo choose the control

Pagina 133 - File Size (FSZ)

Publication AG-UM008C-EN-P - February 20056-14 Configuring MicroLogix 1000 ControllersTable 6.2 DF1 Full-Duplex Configuration Parameters MicroL

Pagina 134 - Retrieving (Reading) Records

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-15Polled Report-by-Exception A slave station can gather i

Pagina 135 - Retrieval Tools

Publication AG-UM008C-EN-P - February 20051-4 Designing Communicationmaster station will continue to poll this slave station until its transmit

Pagina 136

Publication AG-UM008C-EN-P - February 20056-16 Configuring MicroLogix 1000 Controllers• In a point-to-point configuration, the messaging would

Pagina 137 - Conditions that Will Erase

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-17• The MicroLogix 1000 controller uses word addressing, wh

Pagina 138

Publication AG-UM008C-EN-P - February 20056-18 Configuring MicroLogix 1000 ControllersFigure 6.4 Message Timeout Ladder LogicExample MSG Contro

Pagina 139 - Processors

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-19Figure 6.5 Write MSG Instruction from a MicroLogix 1000

Pagina 140 - Installing the Processor

Publication AG-UM008C-EN-P - February 20056-20 Configuring MicroLogix 1000 ControllersFigure 6.6 Read MSG Instruction from a MicroLogix 1000 C

Pagina 141 - Protocols

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1000 Controllers 6-21Figure 6.7 Write MSG Instruction from a MicroLogix 1000

Pagina 142 - Line Drivers

Publication AG-UM008C-EN-P - February 20056-22 Configuring MicroLogix 1000 ControllersFigure 6.8 Read MSG Instruction from a MicroLogix 1000 C

Pagina 143 - Operation

1 Publication AG-UM008C-EN-P - February 2005Chapter 7Configuring Logix Controllers Chapter ObjectivesThis chapter helps you set up a Logix (ControLogi

Pagina 144 - DF1 Half Duplex Master

Publication AG-UM008C-EN-P - February 20057-2 Configuring Logix ControllersOverviewTo configure a Logix controller:1. Install the controller.2.

Pagina 145 - DF1 Radio Modem

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-3Installing the ControllerFor details about installing the controller

Pagina 146 - Parameters

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-5If your SCADA application is time-critical and any two or more of the foll

Pagina 147 - ATTENTION

Publication AG-UM008C-EN-P - February 20057-4 Configuring Logix ControllersDial-up Phone ModemsDial-up phone line modems support point-to-point

Pagina 148 - Half-Duplex Master Station

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-5Line DriversLine drivers, also called short-haul modems, do not actu

Pagina 149

Publication AG-UM008C-EN-P - February 20057-6 Configuring Logix ControllersTable 7.1 Serial Port Parameters and Defaults2. Choose the appropria

Pagina 150

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-7Modem Control Line OperationThe following sections explain the opera

Pagina 151

Publication AG-UM008C-EN-P - February 20057-8 Configuring Logix ControllersConfiguration Considerations for RTS Send and Off DelaysThrough your

Pagina 152 - 19200 0.5 ms/byte

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-9Configuring a Master Station for Standard Polling ModeTo configure t

Pagina 153

Publication AG-UM008C-EN-P - February 20057-10 Configuring Logix ControllersACK Timeout Specifies the amount of time you want the controller to

Pagina 154 - 4.3 on page 4-16 explains

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-11Minimum DF1 Half-Duplex Master ACK TimeoutThe governing timeout par

Pagina 155 - Monitor Active Stations

Publication AG-UM008C-EN-P - February 20057-12 Configuring Logix ControllersDetermining Minimum Master Serial Port ACK TimeoutTo determine the

Pagina 156 - Master Station

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-13DF1 Half-Duplex Master Diagnostic CounterDF1 Half-Duplex Master dri

Pagina 157

Publication AG-UM008C-EN-P - February 20051-6 Designing CommunicationAddressing Tips Each station on the network including the master statio

Pagina 158 -

Publication AG-UM008C-EN-P - February 20057-14 Configuring Logix ControllersTable 7.4 DF1 Half-Duplex Master Diagnostic CountersStatus Field D

Pagina 159

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-15Create Polling List(s) After defining your polling tag(s) and group

Pagina 160 - Configuring a Slave Station

Publication AG-UM008C-EN-P - February 20057-16 Configuring Logix ControllersMonitor Active StationsTo see what stations are active, view the ac

Pagina 161

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-17Configuring a Master Station for Message-based Polling ModeTo confi

Pagina 162

Publication AG-UM008C-EN-P - February 20057-18 Configuring Logix ControllersUse Worksheet 7.2 Logix DF1 Half-Duplex Master Station Configuratio

Pagina 163 - Configuring Channel 0 Poll

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-19Configuring the Controller as a Slave StationTo configure the contr

Pagina 164

Publication AG-UM008C-EN-P - February 20057-20 Configuring Logix ControllersTable 7.6 Define these parameters when configuring a Logix controll

Pagina 165 - Configuring a Radio Modem

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-211. To bring up the Controller Tag interface, click once on the Cont

Pagina 166

Publication AG-UM008C-EN-P - February 20057-22 Configuring Logix ControllersConfiguring the Controller as a Station on a Point-to-Point LinkTo

Pagina 167

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-23Use Table 7.8 to help you understand the screen parameters you need

Pagina 168

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-7SLC 500 Processors with a 1747-KE Module Addressing ConsiderationsSince yo

Pagina 169

Publication AG-UM008C-EN-P - February 20057-24 Configuring Logix ControllersDF1 Point-to-Point Diagnostic CountersDF1 Point-to-Point driver sta

Pagina 170

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-25Accessing DF1 Diagnostic CountersTo access the DF1 diagnostic count

Pagina 171

Publication AG-UM008C-EN-P - February 20057-26 Configuring Logix Controllers Figure 7.5 Viewing Local DF1 Diagnostic CountersFigure 7.6 Resett

Pagina 172

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-27Figure 7.7 Viewing Remote DF1 Diagnostic Counters6. Enter in 1, s f

Pagina 173 - 4.10 on page 4-36 explains

Publication AG-UM008C-EN-P - February 20057-28 Configuring Logix ControllersMessaging Messaging can occur between: • a master station and a sla

Pagina 174

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-29Controller-to-Controller A controller-to-controller message can be

Pagina 175 - Messaging

Publication AG-UM008C-EN-P - February 20057-30 Configuring Logix ControllersConsiderations When Configuring MSG Control BlocksKeep these consid

Pagina 176

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-31• SLC 5/05, SLC 5/04, and SLC 5/03 controllers can respond to PLC5

Pagina 177

Publication AG-UM008C-EN-P - February 20057-32 Configuring Logix ControllersFigure 7.8 Example of a Write MSG from a Logix to a Logix Controlle

Pagina 178

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-33Figure 7.9 Example of a Read MSG from a Logix to a Logix Controller

Pagina 179

Publication AG-UM008C-EN-P - February 20051-8 Designing CommunicationCommunication Scheme Design Using Standard-ModeStandard-communication mode

Pagina 180

Publication AG-UM008C-EN-P - February 20057-34 Configuring Logix ControllersFigure 7.10 Example of a Write MSG From a Logix to a PLC-5 or SLC 5

Pagina 181

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-35Figure 7.11 Example of a Read MSG from a Logix to a PLC-5 or SLC 5

Pagina 182 - Logix controller

Publication AG-UM008C-EN-P - February 20057-36 Configuring Logix ControllersFigure 7.12 Write MSG Instruction From a Logix to an SLC or MicroLo

Pagina 183 - SLC 500 or a MicroLogix

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-37Figure 7.13 Read MSG Instruction from a Logix to an SLC or MicroLog

Pagina 184

Publication AG-UM008C-EN-P - February 20057-38 Configuring Logix ControllersLogix Controller Error Codes for PLC and SLC MessagesWith the relea

Pagina 185

Publication AG-UM008C-EN-P - February 2005Configuring Logix Controllers 7-3900F0 000C F00C Requested function is not available00F0 000D F00D Re

Pagina 186

Publication AG-UM008C-EN-P - February 20057-40 Configuring Logix Controllers

Pagina 187 - Interface Modules

1 Publication AG-UM008C-EN-P - February 2005Chapter 8Configuring ModemsChapter ObjectivesThis chapter provides reference information for help in conne

Pagina 188 - Interface Module

Publication AG-UM008C-EN-P - February 20058-2 Configuring Modems3. Connect the modem to the DTE.For details about how to install, configure, an

Pagina 189 - Configuring the Processor

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-3Figure 8.1 Typical Telephone Modem Configuration Rockwell AutomationRockwell A

Pagina 190

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-9When the master station is configured for standard-communication mode, you

Pagina 191

Publication AG-UM008C-EN-P - February 20058-4 Configuring ModemsThe phone line connection is made through the RJ-45 jack (a phone cable is incl

Pagina 192

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-5DATA-LINC GroupDATA-LINC GROUP supplies telephone modems compatible with Allen-

Pagina 193

Publication AG-UM008C-EN-P - February 20058-6 Configuring Modemsencased in a rugged steel enclosure with large mounting flanges for ease of ins

Pagina 194

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-7unshielded). The range is twenty miles on any ordinary pair wire, or unlimited

Pagina 195

Publication AG-UM008C-EN-P - February 20058-8 Configuring ModemsTable 8.6 LLM1000 Connecting Cable AssembliesDATA-LINC Part Number DescriptionC

Pagina 196 - Save the Configuration

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-9DLM4000The DLM4000 is a stand-alone industrial use modem that communicates with

Pagina 197

Publication AG-UM008C-EN-P - February 20058-10 Configuring ModemsFigure 8.5 DLM4000 Table 8.8 DLM4000 Connecting Cable AssembliesDLM4100-SLC a

Pagina 198

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-11dial-up device. The DLM4100-PLC is a 1746 form factor rack mounted industrial

Pagina 199 - For application See On page

Publication AG-UM008C-EN-P - February 20058-12 Configuring ModemsFigure 8.6 Typical SCADA Configuration Using MARC Leased-Line Modems Figure 8

Pagina 200 - IMPORTANT

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-13Cable Pin AssignmentsThe Model 166-101 requires a RS-232 9-pin D-shell female

Pagina 201

Publication AG-UM008C-EN-P - February 20051-10 Designing CommunicationFigure 1.3 How a Master Station Requests DataTo design a communication s

Pagina 202

Publication AG-UM008C-EN-P - February 20058-14 Configuring ModemsSwitch SettingsFor Bell 202 full-duplex operating mode, set the switches on Mo

Pagina 203

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-15Cable Pin AssignmentsThe Model 137-001 requires a 15-pin male connector with t

Pagina 204

Publication AG-UM008C-EN-P - February 20058-16 Configuring ModemsTable 8.13 Model 137-001 Full-Duplex Switch SettingsTable 8.14 Model 137-001 H

Pagina 205 - Chapter Objectives

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-17Cable Pin AssignmentsThe Model 148-001 requires an RS-232 15-pin male connecto

Pagina 206

Publication AG-UM008C-EN-P - February 20058-18 Configuring ModemsTable 8.16 Model 148-001 Full-Duplex Switch SettingsTable 8.17 Model 148-001

Pagina 207 - 1761-CBL-PM02 Series B Cable

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-19Cable Pin AssignmentsThe Model 166-100 requires a RS-232 9-pin D-shell female

Pagina 208 - Switching

Publication AG-UM008C-EN-P - February 20058-20 Configuring ModemsSwitch SettingsSet the switches on Model 166-100 according to those in Table 8

Pagina 209

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-21Table 8.20 MARC, Inc. Model 166-010 Pin AssignmentsSwitch SettingsThe Model 16

Pagina 210 - Leased-Line Modems

Publication AG-UM008C-EN-P - February 20058-22 Configuring Modemswith some interference. The amount of interference is directly proportional to

Pagina 211

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-23DATA-LINC GroupUse the following table to determine which DATA-LINC radio mode

Pagina 212

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-11Designing a Polling Scheme Each master station in a SCADA application

Pagina 213 - Ownership Timeout

Publication AG-UM008C-EN-P - February 20058-24 Configuring ModemsTo connect the SRM6000 and SRM6100 to the PLC, use a communication cable for y

Pagina 214

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-25Figure 8.15 SRM6200E Front PanelData connection for the SRM6200E is via a RJ45

Pagina 215 - Delay and RTS Off Delay

Publication AG-UM008C-EN-P - February 20058-26 Configuring ModemsThe modems can be configured as master, remote, or repeater (SRM6000/6100-SLC

Pagina 216 - Configuring Poll Timeout

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-27Data connection for the SRM6200E-SLC is via a RJ45 10BAST-T Ethernet port.The

Pagina 217 - Point-to-Point Station

Publication AG-UM008C-EN-P - February 20058-28 Configuring ModemsFigure 8.17 SRM6000-PLC and SRM6100-PLC Front ViewData connection for the SRM6

Pagina 218

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-29Connecting Cable Assemblies Electronic Systems Technology (ESTeem)ESTeem lice

Pagina 219 - Polled Report-by-Exception

Publication AG-UM008C-EN-P - February 20058-30 Configuring ModemsUse the table below to choose the ESTeem model that fits your needs:Figure 8.1

Pagina 220 - Station 2

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-31All ESTeem model 192 wireless modems have the following features or available

Pagina 221

Publication AG-UM008C-EN-P - February 20058-32 Configuring ModemsFigure 8.19 ESTeem Modem Table 8.27 Cable Pin Assignments for ESTeem Radio Mo

Pagina 222

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-331785-KE1747-KE1746-BASKF2 or KF3 modulePCSLC 5/03, 5/04, or 5/05Logix5550or AI

Pagina 223

1 Publication AG-UM008C-EN-P - February 2005Summary of ChangesThe information below summarizes the changes to this manual since the last printing.To h

Pagina 224

Publication AG-UM008C-EN-P - February 20051-12 Designing CommunicationFigure 1.4 The master station scans slave stations in a set sequence.

Pagina 225

Publication AG-UM008C-EN-P - February 20058-34 Configuring ModemsFigure 8.20 ESTeem Switch LocationsTable 8.28 ESTeem Modem RS-232 Switch Setti

Pagina 226

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-35Microwave Data Systems (MDS)MDS supplies radio modems that communicate within

Pagina 227

Publication AG-UM008C-EN-P - February 20058-36 Configuring ModemsMDS Model 2100 and 4100 Master StationsModels 2100 and 4100 are full-duplex, m

Pagina 228 - ™ 5000 programming software

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-37MDS Model 2310 and 4310 Remote StationsModels 2310 and 4310 are multiple addre

Pagina 229 - 9-pin female cable connector

Publication AG-UM008C-EN-P - February 20058-38 Configuring ModemsMDS Model 9810 Spread SpectrumModel 9810 is a spread-spectrum modem, which ope

Pagina 230

Publication AG-UM008C-EN-P - February 2005Configuring Modems 8-39Power Line Modem ConfigurationsPower line modems can also be used for SCADA a

Pagina 231 - Configuring the Controller

Publication AG-UM008C-EN-P - February 20058-40 Configuring ModemsFigure 8.26 LCM100 Connections and Pin AssignmentTable 8.33 LCM100 RS-232 Pin

Pagina 232

1 Publication AG-UM008C-EN-P - February 2005Chapter 9Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsChapter ObjectivesThis chap

Pagina 233

Publication AG-UM008C-EN-P - February 20059-2 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsFigure 9.1 General Driver S

Pagina 234

Publication AG-UM008C-EN-P - February 2005Configuring RSLinx Classic Software for DF1 Half-Duplex Communications 9-3Figure 9.2 Define Polling L

Pagina 235 - Station for Standard Polling

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-13Choosing Single or Multiple Message Transfer Depending on your applica

Pagina 236

Publication AG-UM008C-EN-P - February 20059-4 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsFigure 9.3 Port Configurati

Pagina 237

Publication AG-UM008C-EN-P - February 2005Configuring RSLinx Classic Software for DF1 Half-Duplex Communications 9-5Figure 9.4 DF1 Protocol Set

Pagina 238

Publication AG-UM008C-EN-P - February 20059-6 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsFigure 9.5 Modem Configurat

Pagina 239 - Diagnostic Counter

Publication AG-UM008C-EN-P - February 2005Configuring RSLinx Classic Software for DF1 Half-Duplex Communications 9-7Figure 9.6 Polling Strategi

Pagina 240

Publication AG-UM008C-EN-P - February 20059-8 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsFigure 9.7 Transmitting Str

Pagina 241 - Create Polling List(s)

Publication AG-UM008C-EN-P - February 2005Configuring RSLinx Classic Software for DF1 Half-Duplex Communications 9-9Figure 9.8 Event Log Config

Pagina 242 - Message-Based Mode DF1

Publication AG-UM008C-EN-P - February 20059-10 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsConfiguring RSLinx Classic

Pagina 243 - Polling Mode

Publication AG-UM008C-EN-P - February 2005Configuring RSLinx Classic Software for DF1 Half-Duplex Communications 9-11Figure 9.10 Slave Port Con

Pagina 244

Publication AG-UM008C-EN-P - February 20059-12 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsFigure 9.11 DF1 Slave Prot

Pagina 245

Publication AG-UM008C-EN-P - February 2005Configuring RSLinx Classic Software for DF1 Half-Duplex Communications 9-13Figure 9.12 Slave Modem Co

Pagina 246 - Diagnostic Counters

Publication AG-UM008C-EN-P - February 20051-14 Designing CommunicationFigure 1.6 Effect of MSGs on Logix, PLC-5, SLC 500, and MicroLogix Pol

Pagina 247

Publication AG-UM008C-EN-P - February 20059-14 Configuring RSLinx Classic Software for DF1 Half-Duplex CommunicationsFigure 9.13 Slave Logfile

Pagina 248

1 Publication AG-UM008C-EN-P - February 2005Chapter 10Using Dial-up Telephone CommunicationChapter ObjectivesThis chapter helps you set up and initiat

Pagina 249

Publication AG-UM008C-EN-P - February 200510-2 Using Dial-up Telephone CommunicationOverviewYou can implement dial-up communication in a teleme

Pagina 250 - DF1 Point-to-Point

Publication AG-UM008C-EN-P - February 2005Using Dial-up Telephone Communication 10-3Setting up the SystemBefore you can begin sending messages

Pagina 251 - Counters

Publication AG-UM008C-EN-P - February 200510-4 Using Dial-up Telephone CommunicationConfigure the Modems for MicroLogix 1100/1200/1500 Controll

Pagina 252

Publication AG-UM008C-EN-P - February 2005Using Dial-up Telephone Communication 10-5Initiate Modem Dialing To initiate dialing from a PL

Pagina 253

Publication AG-UM008C-EN-P - February 200510-6 Using Dial-up Telephone CommunicationTo dial a modem from the processor, use an AWA instruction

Pagina 254

Publication AG-UM008C-EN-P - February 2005Using Dial-up Telephone Communication 10-7If the user-configured connection timer times out before th

Pagina 255 - Controller-to-Controller

Publication AG-UM008C-EN-P - February 200510-8 Using Dial-up Telephone CommunicationFigure 10.5 AHL Instructions Lower and Raise DTRPeer-to-Pee

Pagina 256

Publication AG-UM008C-EN-P - February 2005Using Dial-up Telephone Communication 10-9Report-by-Exception and/or Master Station-Initiated Commun

Pagina 257

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-15Communication Scheme Design Using Message-Based ModeIn message-based comm

Pagina 258

Publication AG-UM008C-EN-P - February 200510-10 Using Dial-up Telephone Communication

Pagina 259

1 Publication AG-UM008C-EN-P - February 2005Chapter 11Remotely Program Allen-Bradley Processors Over a Telemetry Network Chapter ObjectivesThis chap

Pagina 260

Publication AG-UM008C-EN-P - February 200511-2 Remotely Program Allen-Bradley Processors Over a Telemetry NetworkRemote Programming via RSLinx®

Pagina 261

Publication AG-UM008C-EN-P - February 2005Remotely Program Allen-Bradley Processors Over a Telemetry Network 11-3Figure 11.2 Configure Remote D

Pagina 262

Publication AG-UM008C-EN-P - February 200511-4 Remotely Program Allen-Bradley Processors Over a Telemetry NetworkRemote Programming via SLC 5/0

Pagina 263

Publication AG-UM008C-EN-P - February 2005Remotely Program Allen-Bradley Processors Over a Telemetry Network 11-5Figure 11.6 Passthru Routing

Pagina 264 - Messages

Publication AG-UM008C-EN-P - February 200511-6 Remotely Program Allen-Bradley Processors Over a Telemetry NetworkFigure 11.8 RSWho Browse to C

Pagina 265

Publication AG-UM008C-EN-P - February 2005Remotely Program Allen-Bradley Processors Over a Telemetry Network 11-7Once RSWho can browse the remo

Pagina 266

Publication AG-UM008C-EN-P - February 200511-8 Remotely Program Allen-Bradley Processors Over a Telemetry NetworkFigure 11.11 Setting Range of

Pagina 267

1 Publication AG-UM008C-EN-P - February 2005Appendix AModem Cable ReferenceAppendix ObjectiveUse this appendix as a quick guide for finding the cables

Pagina 268 - Configurations

Publication AG-UM008C-EN-P - February 20051-16 Designing CommunicationDesigning Communication for DF1 Full-Duplex ProtocolWhen designing commu

Pagina 269 - Rockwell Automation

Publication AG-UM008C-EN-P - February 2005A-2 Modem Cable ReferenceEnhanced PLC-5Figure A.1 Enhanced PLC-5 Processor to Modem Cable Pin Assign

Pagina 270 - 8-4 Configuring Modems

Publication AG-UM008C-EN-P - February 2005Modem Cable Reference A-31747-KE Interface ModuleFigure A.2 1747-KE Interface to Modem Cable Pin Assi

Pagina 271 - DATA-LINC Group

Publication AG-UM008C-EN-P - February 2005A-4 Modem Cable ReferenceASCII Terminal to 1747-KE moduleUse Allen-Bradley cable A-B 1747-CP3 to conn

Pagina 272 - LLM1000-2 and LLM1000-4

Publication AG-UM008C-EN-P - February 2005Modem Cable Reference A-5SLC 5/03, 5/04, or 5/05, Logix, and MicroLogix 1500 Channel 1Figure A.4 SLC

Pagina 273 - Configuring Modems 8-7

Publication AG-UM008C-EN-P - February 2005A-6 Modem Cable Reference1785-KE ModuleUse Allen-Bradley cable A-B 1770-CP to connect a 1785-KE modul

Pagina 274 - 8-8 Configuring Modems

Publication AG-UM008C-EN-P - February 2005Modem Cable Reference A-7MicroLogixUse A-B 1761-PM02 Series B (or higher) (MicroLogix Mini-DIN to 9-p

Pagina 275 - Configuring Modems 8-9

Publication AG-UM008C-EN-P - February 2005A-8 Modem Cable Reference

Pagina 276 - DLM4100-SLC and DLM4100-PLC

1 Publication AG-UM008C-EN-P - February 2005Appendix BBasic DF1 Protocol TroubleshootingAppendix ObjectivesThis appendix helps you troubleshoot commun

Pagina 277 - Company, Inc. (MARC)

Publication AG-UM008C-EN-P - February 2005B-2 Basic DF1 Protocol TroubleshootingIf the MSG instruction errs, follow this troubleshooting sequen

Pagina 278 - MARC Model 166-101

Publication AG-UM008C-EN-P - February 2005Basic DF1 Protocol Troubleshooting B-35. Use the receiving processor’s RS-232 LED to verify that char

Pagina 279 - Cable Pin Assignments

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-17Designing Communication for DF1 Radio Modem ProtocolWhen designing commun

Pagina 280 - MARC Model 137-001

Publication AG-UM008C-EN-P - February 2005B-4 Basic DF1 Protocol TroubleshootingDF1 full- and half-duplex protocols are character-oriented and

Pagina 281 - Switch Settings

Publication AG-UM008C-EN-P - February 2005Basic DF1 Protocol Troubleshooting B-5Table B.2 Identify the DF1 Half-Duplex PacketsSee ANSI X3.4, CC

Pagina 282 - MARC Model 148-001

Publication AG-UM008C-EN-P - February 2005B-6 Basic DF1 Protocol TroubleshootingDF1 Full-Duplex ProtocolTo help you diagnose communication prob

Pagina 283 - MARC #148-001

Publication AG-UM008C-EN-P - February 2005Basic DF1 Protocol Troubleshooting B-7DF1 Radio Modem ProtocolTo help you diagnose communication prob

Pagina 284 - MARC Model 166-100

Publication AG-UM008C-EN-P - February 2005B-8 Basic DF1 Protocol Troubleshooting

Pagina 285

1 Publication AG-UM008C-EN-P - February 2005Appendix CThird-Party Supplier Contact InformationAppendix ObjectivesUse this appendix to help locate the

Pagina 286 - MARC Model 166-010

Publication AG-UM008C-EN-P - February 2005C-2 Third-Party Supplier Contact InformationProSoft Technology, Inc. protocol interfaces for SCADA, p

Pagina 287 - Radio Modem

1 Publication AG-UM008C-EN-P - February 2005Appendix DWorksheetsAppendix ObjectiveUse this appendix to document your serial channel configurations. Ea

Pagina 288

Publication AG-UM008C-EN-P - February 2005D-2 WorksheetsWhen You’re FinishedAfter you complete the worksheets, forward copies to your:• program

Pagina 289

Publication AG-UM008C-EN-P - February 2005Worksheets D-3How to Use the WorksheetsEach SCADA worksheet has different fields that you define, but

Pagina 290

Publication AG-UM008C-EN-P - February 20051-18 Designing CommunicationFigure 1.9 DF1 Radio CommunicationFigure 1.10 Read or Write Requests vi

Pagina 291 - SRM6000/6100/6200E-SLC

Publication AG-UM008C-EN-P - February 2005D-4 WorksheetsWorksheet 1.1 SCADA System SchematicUse this worksheet to sketch your SCADA system, or

Pagina 292

Publication AG-UM008C-EN-P - February 2005Worksheets D-5Worksheet 2.1 Enhanced PLC-5 DF1 Half-Duplex Master Station Configuration Using Standar

Pagina 293 - SRM6000/6100/6200E-PLC

Publication AG-UM008C-EN-P - February 2005D-6 WorksheetsWorksheet 2.2 Enhanced PLC-5 DF1 Half-Duplex Master Station Configuration Using Message

Pagina 294

Publication AG-UM008C-EN-P - February 2005Worksheets D-7Worksheet 2.3 Enhanced PLC-5 DF1 Half-Duplex Slave Station Configuration Use this works

Pagina 295 - Technology (ESTeem)

Publication AG-UM008C-EN-P - February 2005D-8 WorksheetsWorksheet 2.4 Enhanced PLC-5 DF1 Full-Duplex Point-to-Point Configuration Use this work

Pagina 296

Publication AG-UM008C-EN-P - February 2005Worksheets D-9Worksheet 3.1 MicroLogix 1100/1200/1500 DF1 Half-Duplex Master Station Configuration Us

Pagina 297

Publication AG-UM008C-EN-P - February 2005D-10 WorksheetsWorksheet 3.2 MicroLogix 1100/1200/1500 DF1 Half-Duplex Master Station Configuration U

Pagina 298 - (1) ESTeem cable # AA06 (6’)

Publication AG-UM008C-EN-P - February 2005Worksheets D-11Worksheet 3.3 MicroLogix 1100/1200/1500 DF1 Half-Duplex Slave Station ConfigurationUse

Pagina 299 - (1) A-B 1770-CP cable (16.5’)

Publication AG-UM008C-EN-P - February 2005D-12 WorksheetsWorksheet 3.4 MicroLogix 1100/1200/1500 DF1 Full-Duplex Point-to-Point ConfigurationUs

Pagina 300

Publication AG-UM008C-EN-P - February 2005Worksheets D-13Worksheet 3.5 MicroLogix 1100/1200/1500 Radio Modem Slave Station ConfigurationUse thi

Pagina 301

Publication AG-UM008C-EN-P - February 2005Designing Communication 1-19Figure 1.11 Applying Store and Forward in DF1 Radio Modem ProtocolWhat t

Pagina 302

Publication AG-UM008C-EN-P - February 2005D-14 WorksheetsWorksheet 4.1 SLC 5/03, 5/04, and 5/05 DF1 Half-Duplex Master Station Configuration Us

Pagina 303

Publication AG-UM008C-EN-P - February 2005Worksheets D-15Worksheet 4.2 SLC 5/03, 5/04, and 5/05 DF1 Half-Duplex Master Station Configuration Us

Pagina 304

Publication AG-UM008C-EN-P - February 2005D-16 WorksheetsWorksheet 4.3 SLC 5/03, 5/04, and 5/05 DF1 Half-Duplex Slave Station ConfigurationUse

Pagina 305 - Power Line Modem

Publication AG-UM008C-EN-P - February 2005Worksheets D-17Worksheet 4.4 SLC 5/03, 5/04, and 5/05 DF1 Full-Duplex Point-to-Point ConfigurationUse

Pagina 306 - Serial Number:

Publication AG-UM008C-EN-P - February 2005D-18 WorksheetsWorksheet 4.5 SLC 5/03, 5/04, and 5/05 DF1 Radio Modem Station ConfigurationUse this w

Pagina 307 - Half-Duplex Communications

Publication AG-UM008C-EN-P - February 2005Worksheets D-19Worksheet 5.1 SLC 500 Processor with 1747-KE Module DF1 Half-Duplex Slave Station Conf

Pagina 308

Publication AG-UM008C-EN-P - February 2005D-20 WorksheetsWorksheet 5.2 SLC 500 Processor with 1747-KE Module Point-to-Point ConfigurationUse th

Pagina 309

Publication AG-UM008C-EN-P - February 2005Worksheets D-21Worksheet 6.1 MicroLogix 1000 DF1 Half-Duplex Slave Station ConfigurationUse this work

Pagina 310

Publication AG-UM008C-EN-P - February 2005D-22 WorksheetsWorksheet 7.1 Logix DF1 Half-Duplex Master Station Configuration Using Standard Commun

Pagina 311

Publication AG-UM008C-EN-P - February 2005Worksheets D-23Worksheet 7.2 Logix DF1 Half-Duplex Master Station Configuration Using Message-based C

Pagina 312

Publication AG-UM008C-EN-P - February 20051-20 Designing Communication

Pagina 313

Publication AG-UM008C-EN-P - February 2005D-24 WorksheetsWorksheet 7.3 Logix DF1 Half-Duplex Slave Station Configuration Use this worksheet to

Pagina 314

Publication AG-UM008C-EN-P - February 2005Worksheets D-25Worksheet 7.4 Logix DF1 Full-Duplex Point-to-Point ConfigurationUse this worksheet to

Pagina 315

Publication AG-UM008C-EN-P - February 2005D-26 Worksheets

Pagina 316 - Version 2.x as a Slave

1 Publication AG-UM008C-EN-P - February 2005Appendix ESample Ladder LogicAppendix ObjectiveThis appendix provides guidance for developing your messagi

Pagina 317

Publication AG-UM008C-EN-P - February 2005E-2 Sample Ladder LogicSLC DF1 Half-Duplex Master Standard Mode, Master-initiated MSGSLC 5/03/04/05 D

Pagina 318

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-3The following two rungs are the MSG control rungs - they should be replicated

Pagina 319

Publication AG-UM008C-EN-P - February 2005E-4 Sample Ladder LogicSLC DF1 Half-Duplex Master Message-based Mode and DF1 Radio Modem initiated MS

Pagina 320

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-5The following two rungs are the MSG control rungs - they should be replicated

Pagina 321

Publication AG-UM008C-EN-P - February 2005E-6 Sample Ladder LogicSLC DF1 Half-Duplex Slave and DF1 Radio Modem Report-by-Exception MSGSLC DF1 H

Pagina 322

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-7JMPQ2:2Jump toMSG RungIf the current value comparison finds no differences, in

Pagina 323 - Setting up the System

1 Publication AG-UM008C-EN-P - February 2005Chapter 2Configuring Enhanced PLC-5 Processors Chapter ObjectivesThis chapter helps you set up an Enhanced

Pagina 324 - Telephone Line

Publication AG-UM008C-EN-P - February 2005E-8 Sample Ladder LogicPLC-5 and MicroLogix 1100/1200/1500 DF1 Half-Duplex Master Standard Mode, Mast

Pagina 325 - Figure 10.3 AWA Instruction

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-90006B3:03DisableMSG #3ENDNERMSGRead/Write MessageControl MG9:3Setup ScreenMSG0

Pagina 326

Publication AG-UM008C-EN-P - February 2005E-10 Sample Ladder LogicPLC-5 and MicroLogix 1100/1200/1500 DF1 Half-Duplex Master Message-based, Mas

Pagina 327 - Transfer Data

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-110006B3:03DisableMSG #3ENDNERMSGRead/Write MessageControl MG9:3Setup ScreenMSG

Pagina 328 - Communication

Publication AG-UM008C-EN-P - February 2005E-12 Sample Ladder LogicPLC-5 and MicroLogix 1100/1200/1500 DF1 Half-Duplex Slave Report-by-Exception

Pagina 329 - Master Station-Initiated

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-13If any values differ between the first five words of B3:0 and N7:0, copy B3:0

Pagina 330

Publication AG-UM008C-EN-P - February 2005E-14 Sample Ladder LogicMicroLogix 1000 Analog DF1 Half-Duplex Slave Report-by-Exception MSGMicroLogi

Pagina 331 - Over a Telemetry Network

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-15The next three rungs create a data file comparison routine. This rung clears

Pagina 332 - Gateway

Publication AG-UM008C-EN-P - February 2005E-16 Sample Ladder LogicLogix DF1 Half-Duplex Master Standard Mode, Master-Initiated MSGEach MSG is a

Pagina 333

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-1725 MSG to Slave #12Message12.EN MSG to Slave #12Message12.DN MSG to Slave #12

Pagina 334 - Passthru

Publication AG-UM008C-EN-P - February 20052 Summary of Changes

Pagina 335

Publication AG-UM008C-EN-P - February 20052-2 Configuring Enhanced PLC-5 ProcessorsFigure 2.1 Configuring and Enhanced PLC-5Installing the Pro

Pagina 336

Publication AG-UM008C-EN-P - February 2005E-18 Sample Ladder Logic37/Disable_MSG[18]ENDNERType - PLC5 Typed ReadMessage Control Message18 ... M

Pagina 337 - Logix EtherNet/IP to DF1

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-19Logix DF1 Half-Duplex Master Message-based Mode, Master-Initiated MSGLogix555

Pagina 338

Publication AG-UM008C-EN-P - February 2005E-20 Sample Ladder Logic24/Disable_MSG[12]ENDNERType - PLC5 Typed ReadMessage Control Message12 ... M

Pagina 339 - Modem Cable Reference

Publication AG-UM008C-EN-P - February 2005Sample Ladder Logic E-21Logix DF1 Half-Duplex Slave Report-By-Exception MSGLogix5550 DF1 Half-Duplex

Pagina 340 - Enhanced PLC-5

Publication AG-UM008C-EN-P - February 2005E-22 Sample Ladder Logic

Pagina 341 - 1747-KE Interface Module

1 Publication AG-UM008C-EN-P - February 2005GlossaryACK See Acknowledgment.Acknowledgment An ASCII control character that indicates the transmission a

Pagina 342 - ASCII Terminal to 1747-KE

Publication AG-UM008C-EN-P - February 20052 Glossary DSR Data-set Ready. A signal from the modem that indicates the modem is connected

Pagina 343 - Channel 1

Publication AG-UM008C-EN-P - February 2005Glossary 3Half-Duplex Protocol 1) A mode of operation for a point-to-point or multipoint baseband lin

Pagina 344 - 1785-KE Module

Publication AG-UM008C-EN-P - February 20054 Glossary Packet Radio Modem An intelligent radio modem that packetizes the data it receive

Pagina 345 - MicroLogix

Publication AG-UM008C-EN-P - February 2005Glossary 5RXD Received Data. A serialized data input to a receiving device.Remote Station A device (p

Pagina 346

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-3The DF1 Point-to-Point Station Address of the processor is t

Pagina 347 - Troubleshooting

Publication AG-UM008C-EN-P - February 20056 Glossary Notes:

Pagina 348

Publication AG-UM008C-EN-P - February 2005IndexNumerics1747-KE 1-7, 5-1, 5-4, 5-5, 5-8, 5-11AddressingGroup size 1-7Configuring 5-7, 5-9SLC 5/01 and 5

Pagina 349 - DF1 Protocol

Publication AG-UM008C-EN-P - February 20052 Indexconfiguring SLC 5/03, 5/04, and 5/05 full-duplex station 4-28, 4-34configuring SLC 5/03, 5/04,

Pagina 350 - DF1 Half-Duplex Protocol

Publication AG-UM008C-EN-P - February 2005Index 3EEmbedded responsesMicroLogix 1100/1200/1500 3-34SLC 5/01 and 5/02 5-10SLC-5/03, 5/04, and 5/0

Pagina 351

Publication AG-UM008C-EN-P - February 20054 Indexcontrol symbols B-4Half-duplex circuit Glossary-2Half-duplex modem Glossary-2Half-duplex proto

Pagina 352 - DF1 Full-Duplex Protocol

Publication AG-UM008C-EN-P - February 2005Index 5Getting MicroLogix 1000 processors to accept byte offsets 6-17MSGconfiguration considerations

Pagina 353 - DF1 Radio Modem Protocol

Publication AG-UM008C-EN-P - February 20056 IndexMicroLogix 1100/1200/1500 3-37SLC 5/01 and 5/02 5-12SLC 5/03, 5/04 or 5/05 4-38Multidrop linkd

Pagina 354

Publication AG-UM008C-EN-P - February 2005Index 7Remote station driverMicroLogix 1100/1200/1500 3-13, 3-21, 3-23, 3-40SLC 5/01 and 5/02 5-7SLC

Pagina 355 - Contact List

Publication AG-UM008C-EN-P - February 20058 IndexPolled Report-by-Exception 4-37Processor-to-Processor 4-38Standard Polling Mode 4-40Modems 4-3

Pagina 356

Publication AG-UM008C-EN-P - February 2005Index 9

Pagina 357 - Worksheets

Publication AG-UM008C-EN-P - February 20052-4 Configuring Enhanced PLC-5 ProcessorsTo configure the processor for a master station using standa

Pagina 358 - When You’re Finished

Publication AG-UM008C-EN-P - February 2005 11Supersedes Publication AG-6.5.8 - October 1998 Copyright © 2005 Rockwell Automation, Inc. All rights rese

Pagina 359 - How to Use the Worksheets

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-5Define the Communication Driver Characteristics Use Table 2.

Pagina 360 - SCADA System Schematic

Publication AG-UM008C-EN-P - February 20052-6 Configuring Enhanced PLC-5 ProcessorsOptions Station Address Define the octal address of the pro

Pagina 361 - Page 1 of 1

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-7Displaying System (Master) Channel StatusPolling Normal Poll

Pagina 362

Publication AG-UM008C-EN-P - February 20052-8 Configuring Enhanced PLC-5 ProcessorsTable 2.2 Descriptions of System Mode DF1 Master Channel Sta

Pagina 363 - Configuration

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-9The normal and priority poll file layout is as follows: T

Pagina 364 - Full-Duplex Point-to-Point

Publication AG-UM008C-EN-P - February 20052-10 Configuring Enhanced PLC-5 ProcessorsFigure 2.3 is an example of a station list containing three

Pagina 365

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-11Configuring a DF1 Half-Duplex Message-based Mode Master Sta

Pagina 366

1 Publication AG-UM008C-EN-P - February 2005Table of ContentsPrefaceWhat SCADA Information Is Available?. . . . . . . . . . . . . . . . 1-1Audience

Pagina 367 - Station Configuration

Publication AG-UM008C-EN-P - February 20052-12 Configuring Enhanced PLC-5 ProcessorsUse Table 2.3 to help you understand the communication para

Pagina 368

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-13Serial Port Control Line This parameter defines the mode in

Pagina 369 - Radio Modem Slave Station

Publication AG-UM008C-EN-P - February 20052-14 Configuring Enhanced PLC-5 ProcessorsPolling Polling Mode If you want to:• accept unsolicited me

Pagina 370

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-15Configuring the Processor as a Slave Station To configure t

Pagina 371

Publication AG-UM008C-EN-P - February 20052-16 Configuring Enhanced PLC-5 ProcessorsTable 2.4 Communication Parameters for a PLC-5 Slave Stati

Pagina 372 - SLC 5/03, 5/04, and 5/05 DF1

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-17Options Station Address Define the octal address of the pro

Pagina 373

Publication AG-UM008C-EN-P - February 20052-18 Configuring Enhanced PLC-5 ProcessorsDisplaying Slave System Channel StatusTable 2.5 Description

Pagina 374 - Radio Modem Station

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-19Undelivered Messages word 3 The number of messages that wer

Pagina 375

Publication AG-UM008C-EN-P - February 20052-20 Configuring Enhanced PLC-5 ProcessorsConfiguring the Processor as a Station on a Point-to-Point

Pagina 376

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-21Table 2.6 Configuring the PLC-5 Processor as a Device on a

Pagina 377 - MicroLogix 1000 DF1

Publication AG-UM008C-EN-P - February 20052 Table of Contents Configuring the Processor as a Station on a Point-to-Point Link . . . .

Pagina 378

Publication AG-UM008C-EN-P - February 20052-22 Configuring Enhanced PLC-5 ProcessorsDisplaying Point-to-Point System Channel StatusTable 2.7 D

Pagina 379

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-23MessagingMessaging can occur between: • a master station an

Pagina 380 - Slave Station Configuration

Publication AG-UM008C-EN-P - February 20052-24 Configuring Enhanced PLC-5 ProcessorsProcessor-to-Processor A processor-to-processor message

Pagina 381

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-25Considerations When Configuring MSG Control Blocks Kee

Pagina 382 - D-26 Worksheets

Publication AG-UM008C-EN-P - February 20052-26 Configuring Enhanced PLC-5 ProcessorsExample MSG Control Blocks Figure 2.5 Example of a PLC-

Pagina 383

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-27Figure 2.6 Example of a PLC-5 Write MSG to Another PLC-5 (

Pagina 384

Publication AG-UM008C-EN-P - February 20052-28 Configuring Enhanced PLC-5 ProcessorsFigure 2.7 Example of a PLC-5 Read MSG to an SLC 500 or Mic

Pagina 385

Publication AG-UM008C-EN-P - February 2005Configuring Enhanced PLC-5 Processors 2-29Figure 2.8 Example of a PLC-5 Write MSG to an SLC 500 or M

Pagina 386

Publication AG-UM008C-EN-P - February 20052-30 Configuring Enhanced PLC-5 Processors

Pagina 387

1 Publication AG-UM008C-EN-P - February 2005Chapter 3Configuring MicroLogix 1100/1200/1500 ControllersChapter ObjectivesThis chapter helps you set up

Pagina 388

Publication AG-UM008C-EN-P - February 2005Table of Contents 3Configuring a Station on a Point-to-Point Link . . . . . . . . . . 3-33DF1 Full-Du

Pagina 389

Publication AG-UM008C-EN-P - February 20053-2 Configuring MicroLogix 1100/1200/1500 ControllersOverviewTo configure a MicroLogix 1100/1200/1500

Pagina 390 - Master-initiated MSG

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-3MicroLogix 1200/1500 Channel 0 Cable Pinouts - U

Pagina 391

Publication AG-UM008C-EN-P - February 20053-4 Configuring MicroLogix 1100/1200/1500 ControllersMicroLogix 1200/1500 Channel 0 Cable Pinouts - A

Pagina 392

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-5MicroLogix 1500 LRP Channel 1 Cable PinoutsFigur

Pagina 393

Publication AG-UM008C-EN-P - February 20053-6 Configuring MicroLogix 1100/1200/1500 ControllersUsing Modems that Support DF1 Communication Prot

Pagina 394

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-7Leased-Line ModemsLeased-line modems are used wi

Pagina 395

Publication AG-UM008C-EN-P - February 20053-8 Configuring MicroLogix 1100/1200/1500 ControllersModem Control Line OperationThe following explai

Pagina 396

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-9DF1 Half Duplex MasterWhen configuring for DF1 h

Pagina 397

Publication AG-UM008C-EN-P - February 20053-10 Configuring MicroLogix 1100/1200/1500 ControllersHalf-Duplex Modem with DCD Handshaking (MicroLo

Pagina 398

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-11Configuring DF1 Half-Duplex Channel 0 Parameter

Pagina 399 - Rungs 4-23 have been omitted

Publication AG-UM008C-EN-P - February 20054 Table of Contents Configuring DF1 Half-Duplex Channel 0 Parameters. . . . . . 4-8RTS Sen

Pagina 400

Publication AG-UM008C-EN-P - February 20053-12 Configuring MicroLogix 1100/1200/1500 ControllersConfiguring a Standard-Mode DF1 Half-Duplex Mas

Pagina 401

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-13 Table 3.1 MicroLogix 1100/1200/1500 Maste

Pagina 402 - Rungs 6-23 have been omitted

Publication AG-UM008C-EN-P - February 20053-14 Configuring MicroLogix 1100/1200/1500 ControllersMinimum DF1 Half-Duplex Master Channel 0 ACK Ti

Pagina 403

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-15To calculate the minimum ACK timeout, you must

Pagina 404

Publication AG-UM008C-EN-P - February 20053-16 Configuring MicroLogix 1100/1200/1500 ControllersFinally, you must determine the larger of two v

Pagina 405

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-17DF1 Half-Duplex Master Channel StatusChannel St

Pagina 406 - 2 Glossary

Publication AG-UM008C-EN-P - February 20053-18 Configuring MicroLogix 1100/1200/1500 ControllersMonitor Active Stations To see what slave

Pagina 407 - Glossary 3

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-19If you are using RSLogix 500 version 6.10.10 or

Pagina 408 - 4 Glossary

Publication AG-UM008C-EN-P - February 20053-20 Configuring MicroLogix 1100/1200/1500 ControllersTo configure the processor for a master station

Pagina 409 - Glossary 5

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-21Define the parameters shown in Table 3.4 when c

Pagina 410 - 6 Glossary

Publication AG-UM008C-EN-P - February 2005Table of Contents 5Chapter 6Configuring MicroLogix 1000 ControllersChapter Objectives . . . . . . . .

Pagina 411 - Numerics

Publication AG-UM008C-EN-P - February 20053-22 Configuring MicroLogix 1100/1200/1500 ControllersConfiguring a Slave Station To choose the proce

Pagina 412 - 2 Index

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-23Use Worksheet 3.3 MicroLogix 1100/1200/1500 DF1

Pagina 413 - Index 3

Publication AG-UM008C-EN-P - February 20053-24 Configuring MicroLogix 1100/1200/1500 ControllersDuplicate Packet Detect Duplicate Detect lets t

Pagina 414 - 4 Index

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-25Configuring Poll TimeoutThe Poll Timeout is onl

Pagina 415 - Index 5

Publication AG-UM008C-EN-P - February 20053-26 Configuring MicroLogix 1100/1200/1500 ControllersMessages Retried CSx:13 The number of message r

Pagina 416 - 6 Index

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-27Configuring a Radio Modem StationTo configure a

Pagina 417 - Index 7

Publication AG-UM008C-EN-P - February 20053-28 Configuring MicroLogix 1100/1200/1500 ControllersTable 3.7 Define these communication parameters

Pagina 418 - 8 Index

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-29RTS On Delay0 Defines the amount of time, in 20

Pagina 419 - Index 9

Publication AG-UM008C-EN-P - February 20053-30 Configuring MicroLogix 1100/1200/1500 ControllersDF1 Radio Modem Channel StatusChannel status da

Pagina 420 - Installation Assistance

Publication AG-UM008C-EN-P - February 2005Configuring MicroLogix 1100/1200/1500 Controllers 3-31For the MicroLogix 1500 LRP, clicking the Clear