Remotely Program Allen-Bradley Processors Over a Telemetry Network 11-5
Figure 11.6 Passthru Routing Table Icon
Double-click on Routing Table to view and modify the passthru
routing table. The IP address of the PC running RSLinx Classic must be
entered into the passthru routing table in order for RSWho to be able
to browse through the SLC 5/05.
Figure 11.7 Passthru Routing Table Configuration
Configure the RSLinx AB_ETH Ethernet driver and run RSWho to
browse the passthru SLC 5/05 on this network and click on the ‘+’ sign
in front of the SLC 5/05 to reveal a Channel 0, DF1 network
underneath.
TIP
If the ‘+’ sign doesn’t show up in front of the
SLC 5/05, then either bit S:34/5 is not set in the
processor, the processor firmware is not OS501,
Series C, FRN 6 or greater, the RSLinx version is not
2.43 or later, or channel 0 is not set to a valid
passthru DF1 driver.