Publication AG-UM008C-EN-P - February 2005
11-4 Remotely Program Allen-Bradley Processors Over a Telemetry Network
Remote Programming via
SLC 5/05 Ethernet to DF1
Passthru
SLC 5/05 processors with OS 501, Series C, FRN 6 or higher firmware
support channel 1 Ethernet to channel 0 DF1 passthru. This allows
PCs running RSLinx Classic version 2.43, or higher, to browse through
the SLC 5/05 processor to remote PLC-5, SLC or MicroLogix processors
on the DF1 network to upload, download or go online using RSLogix
programming software. This capability is supported when the
SLC 5/05 channel 0 driver is DF1 Full-Duplex, DF1 Half-Duplex
Master or DF1 Radio Modem
To configure passthru on the SLC 5/05, the DF1 Gateway Enable Bit,
S:34/5, must be set and the Passthru Routing Table File number must
be configured within the Channel 1 Channel Configuration.
Figure 11.4 DF1 Gateway Enable Bit
Figure 11.5 Passthru Routing Table File Number
After configuring the Pass Thru Routing Table File number, access to
the passthru routing table is located underneath the Channel
Configuration selection in RSLogix 500. Click on the ‘+’ sign in front of
Channel Configuration to reveal the routing table selection.
TIP
Although SLC 5/05 passthru can be used to browse
Logix processors, it cannot be used to upload,
download or go online with Logix processors.