Publication AG-UM008C-EN-P - February 2005
Configuring SLC 5/03, 5/04, and 5/05 Processors 4-33
Configuring a Station on a
Point-to-Point Link
To configure the processor for point-to-point communication, follow
the steps below using your programming software.
1. To bring up the Channel
Configuration interface,
double-click on the Channel
Configuration icon.
2. Define the location of the
diagnostic file used for
Channel Status here. See
Table 4.10 on page 4-36 for
diagnostic file details.