3.2. Complex I/O Equipment Definition
A
ll Trusted
T
M
s
ystems require a processor definition in the I/O Connection Table. Details of how to edit
the I/O Connection table are given in PD-8082B. The structure of the definition is given below.
3.2.1. I/O Complex Equipment ‘TTMRP’
Description: Trusted
TM
TMR Processor. This definition will open a single TMR Processor module.
Only one installation is allowed. The data attached will give the application access to
the user LEDs, real time clock and external analogue data from the system.
OEM PARAMETERS
OEM parameter Valid numbers Description
TICS_CHASSIS
TICS_SLOT
1 – 15
0
The TICS chassis & slot number where the TMR Processor module is
placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1: [TTMRP_0]
16 ANALOGUE Inputs
Channel 1:
Module temperature
(t
enths of degrees C)
Channel 2
24V
dc feed 1 after protection diodes
Channel 3
24V
dc feed 2 after protection diodes
Channel 4
FRCA 8V
dc supply
Channel 5
FRCB 8V
dc supply
Channel 6
FRCC 8V
dc supply
Channel 7
16
-
bit sc
an count
Channel 8
16
-
bit scan count
Channel 9
Number of locked variables in the application
Channels 10
16
Reserved
RACK 2: [TTMRP_1]
16 BOOLEAN Inputs
Channel 1 PSU-A Output Status TRUE = Fail, FALSE = Pass
Channel 2 PSU-B Output Status TRUE = Fail, FALSE = Pass
Channel 3 PSU-A Line Status TRUE = Low Voltage Warning, FALSE = OK
Channel 4 PSU-B Line Status TRUE = Low Voltage Warning, FALSE = OK
Channel 5 IRIG Input Status TRUE = Pass, FALSE = Fail
Channel 6 System Health TRUE = Fail, FALSE = Healthy
Channel 7 Reset Pushbutton Status TRUE (one-shot) = pressed
Channel 8 Keyswitch Status TRUE = Run, FALSE = Maintain
Channel 9 - 16 Not used
RACK 3: [TTMRP_2]
16 BOOLEAN outputs
Channel 1 This channel drives the USER LED 1.
TRUE = USER LED 1 ON, FALSE = USER LED 1 OFF
Channel 2 This channel drives the USER LED 2.
TRUE = USER LED 2 ON, FALSE = USER LED 2 OFF
Channel 3 Unlock all channels, edge triggered on a (FALSE -> TRUE) change
Channel 4 System Healthy LED controls. TRUE = Unhealthy, FALSE = Healthy.
Channel 5 USER LED 1 Colour. TRUE = Green, FALSE = Red.
Channel 6 USER LED 2 Colour. TRUE = Green, FALSE = Red.
Channels 7 – 16 Not used