Rockwell-automation T8424 Trusted TMR 120Vac Digital Input Module Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 29
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Trusted
TM
Module T8424
Issue 8 Sep 11 PD-T8424 17
3.2.5. Rack 5: LINE_FLT
Channel Description
1 Field input channel 1 line fault
2 Field input channel 2 line fault
40 Field input channel 40 line fault
Table 8 Rack 5: Line Fault descriptions
The line fault input is reported as true (logic1) for a line fault condition (for this module, only FTA to
module Open Circuit). The logic state is the majority voted value.
When the TMR Processor detects a 2oo3 channel fault or discrepancy, or if the input module is
simulated, the line fault input is set to True.
3.2.6. Rack 6: DISCREP
Channel Description
1 Discrepancy status inputs 1 to 16 (input 1 is LSB, bit 0)
2 Discrepancy status inputs 17 to 32 (input 17 is LSB, bit 0)
3 Discrepancy status inputs 33 to 40 (input 33 is LSB, bit 0)
Table 9 Rack 6: DISCREP bit descriptions
Each of the integers reports the discrepancy status of 16 input channels. The corresponding bit within
the integer is set to1 when a discrepancy condition is detected on that input channels input state
(rack 2). For example, if slice B of the input module reports the state of channel 4 as state 5, while
slices A and C report channel 4 as state 2, then Slice B has a channel discrepancy for channel 4. In
this case, bit 3 of channel 1 on the Discrepancy board would be set to ‘1’.