Rockwell-automation T8424 Trusted TMR 120Vac Digital Input Module Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 29
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
Trusted
TM
Module T8424
Issue 8 Sep 11 PD-T8424 18
3.2.7. Rack 7: HKEEPING
Channel
Description
FCR Units (Full Scale Range)
1
A
24V2 Input Voltage -32768 32767 mV
2
B
3
4
A
Internal supply voltage (post regulator) -32768 32767 mV
5
B
6
7
A
Internal supply current (post regulator) -32768 32767 mA
8
B
9
10
A
Input voltage (post isolation) -32768 32767 mV
11
B
12
13
A
24V1 Input Voltage -32768 32767 mV
14
B
15
16
A
HIU Board Temperature
(Note: Temperature, ºC = input value / 256)
-32768 32767 -
17
B
18
19
A
Front Panel Load Current -32768 32767 mA
20
B
21
22
A
SmartSlot Link Voltage -32768 32767 mV
23
B
24
25
A
Reserved for FIU condensation sensor 0 0 -
26
B
27
28
A
FIU Internal Supply Voltage -32768 32767 mV
29
B
30
31
A
FIU Internal Supply Current -32768 32767 mA
32
B
33
34
A
FIU Unregulated input voltage -32768 32767 mV
35
B
36
37
A
FIU Board Temperature
(Note: Temperature, ºC = input value / 256)
-32768 32767 -
38
B
39
40
A
FIU Reference Voltage, DAC_X1 -32768 32767 mV
41
B
42
43
A
FIU Reference Voltage, DAC_X2 -32768 32767 mV
44
B
45
46
A
FIU Reference Voltage, DAC_X3 -32768 32767 mV
47
B
48
49
A
Diagnostic error code
50
B
51
Table 10 Rack 7: Housekeeping descriptions